| 1 | 2 | 3 | 4 | 5 |
AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFEAT SEA, 1974
AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFEAT SEA, 1974
.2.8 Ventilation arrangements to the space containing the
independent source of power for the emergency fire pump shall be such as
to preclude, as far as practicable, the possibility of smoke from a
machinery space fire entering or being drawn into that space.
.3 In passenger ships of less than 1,000 tons gross tonnage and
cargo ships of less than 2,000 tons gross tonnage, if a fire in any one
compartment could put all the pumps out of action the alternative means of
providing water for fire-fighting purposes are to the satisfaction of the
Administration.
.4 In addition, in cargo ships where other pumps, such as general
service, bilge and ballast, etc., are fitted in a machinery space,
arrangements shall be made to ensure that at least one of these pumps,
having the capacity and pressure required by paragraphs 2.2 and 4.2, is
capable of providing water to the fire main.
3.4 The arrangements for the ready availability of water supply shall
be:
.1 in passenger ships of 1,000 tons gross tonnage and upwards such
that at least one effective jet of water is immediately available from any
hydrant in an interior location and so as to ensure the continuation of
the output of water by the automatic starting of a required fire pump;
.2 in passenger ships of less than 1,000 tons gross tonnage and in
cargo ships to the satisfaction of the Administration;
.3 in cargo ships with a periodically unattended machinery space
or when only one person is required on watch there shall be immediate
water delivery from the fire main system at a suitable pressure, either by
remote starting of one of the main fire pumps with remote starting from
the navigating bridge and fire control station, if any, or permanent
pressurization of the fire main system by one of the main fire pumps,
except that the Administration may waive this requirement for cargo ships
of less than 1,600 tons gross tonnage if the arrangement of the machinery
space access makes it unnecessary;
.4 in passenger ships, if fitted with periodically unattended
machinery spaces in accordance with Regulation II-1/54, the Administration
shall determine provisions for fixed water fire-extinguishing arrangement
for such spaces equivalent to those required for normally attended
machinery spaces.
3.5 Relief valves shall be provided in conjunction with all fire pumps
if the pumps are capable of developing a pressure exceeding the design
pressure of the water service pipes, hydrants and hoses. These valves
shall be so placed and adjusted as to prevent excessive pressure in any
part of the fire main system.
3.6 In tankers isolation valves shall be fitted in the fire main at
poop front in a protected position and on the tank deck at intervals of
not more than 40 m to preserve the integrity of the fire main system in
case of fire or explosion.
4 Diameter of and pressure in the fire mains
4.1 The diameter of the fire main and water service pipes shall be
sufficient for the effective distribution of the maximum required
discharge from two fire pumps operating simultaneously, except that in
the case of cargo ships the diameter need only be sufficient for the
3 discharge of 140 m / hour.
4.2 With the two pumps simultaneously delivering through nozzles
specified in paragraph 8 the quantity of water specified in paragraph 4.1,
through any adjacent hydrants, the following minimum pressures shall be
maintained at all hydrants:
Passenger ships:
4,000 tons gross tonnage and upwards 0.31 N /square mm
1,000 tons gross tonnage and upwards 0.27 N /square mm
but under 4,000 tons gross tonnage
Under 1,000 tons gross tonnage To the satisfaction
of the
Administration
Cargo ships:
6,000 tons gross tonnage and upwards 0.27 N/square mm
1,000 tons gross tonnage and upwards 0.25 N/square mm
but under 6,000 tons gross tonnage
Under 1,000 tons gross tonnage To the satisfaction
of the
Administration
4.3 The maximum pressure at any hydrant shall not exceed that at which
the effective control of a fire hose can be demonstrated.
5 Number and position of hydrants
5.1 The number and position of hydrants shall be such that at least
two jets of water not emanating from the same hydrant, one of which shall
be from a single length of hose, may reach any part of the ship normally
accessible to the passengers or crew while the ship is being navigated and
any part of any cargo space when empty, any ro/ro cargo space or any
special category space in which latter case the two jets shall reach any
part of such space, each from a single length of hose. Furthermore, such
hydrants shall be positioned near the accesses to the protected spaces.
5.2 In the accommodation, service and machinery spaces of passenger
ships the number and position of hydrants shall be such that the
requirements of paragraph 5.1 may be complied with when all watertight
doors and all doors in main vertical zone bulkheads are closed.
5.3 Where, in a passenger ship, access is provided to a machinery
space of category A at a low level from an adjacent shaft tunnel, two
hydrants shall be provided external to, but near the entrance to that
machinery space. Where such access is provided from other spaces, in one
of those spaces two hydrants shall be provided near the entrance to the
machinery space of category A. Such provision need not be made where the
tunnel or adjacent spaces are not part of the escape route.
6 Pipes and hydrants
6.1 Materials readily rendered ineffective by heat shall not be used
for fire mains and hydrants unless adequately protected. The pipes and
hydrants shall be so placed that the fire hoses may be easily coupled to
them. The arrangement of pipes and hydrants shall be such as to avoid the
possibility of freezing. In ships where deck cargo may be carried, the
positions of the hydrants shall be such that they are always readily
accessible and the pipes shall be arranged as far as practicable to avoid
risk of damage by such cargo. Unless one hose and nozzle is provided for
each hydrant in the ship, there shall be complete interchange ability of
hose couplings and nozzles.
6.2 A valve shall be fitted to serve each fire hose so that any fire
hose may be removed while the fire pumps are at work.
6.3 Isolating valves to separate the section of the fire main within
the machinery space containing the main fire pump or pumps from the rest
of the fire main shall be fitted in an easily accessible and tenable
position outside the machinery spaces. The fire main shall be so arranged
that when the isolating valves are shut all the hydrants on the ship,
except those in the machinery space referred to above, can be supplied
with water by a fire pump not located in this machinery space through
pipes which do not enter this space. Exceptionally, the Administration may
permit short lengths of the emergency fire pump suction and discharge
piping to penetrate the machinery space if it is impracticable to route it
externally provided that the integrity of the fire main is maintained by
the enclosure of the piping in a substantial steel casing.
7 Fire hoses
7.1 Fire hoses shall be of material approved by the Administration and
shall be sufficient in length to project a jet of water to any of the
spaces in which they may be required to be used. Their maximum length
shall be to the satisfaction of the Administration. Each hose shall be
provided with a nozzle and the necessary couplings. Hoses specified in
this Chapter as "fire hoses" shall together with any necessary fittings
and tools be kept ready for use in conspicuous positions near the water
service hydrants or connexions. Additionally in interior locations in
passenger ships carrying more than 36 passengers fire hoses shall be
connected to the hydrants at all times.
7.2 Ships shall be provided with fire hoses the number and diameter of
which shall be to the satisfaction of the Administration.
7.3 In passenger ships there shall be at least one fire hose for each
of the hydrants required by paragraph 5 and these hoses shall be used only
for the purposes of extinguishing fires or testing the fire-extinguishing
apparatus at fire drills and survey s.
7.4.1 In cargo ships of 1,000 tons gross tonnage and upwards the
number of fire hoses to be provided shall be one for each 30 m length of
the ship and one spare but in no case less than five in all. This number
does not include any hoses required in any engine or boiler room. The
Administration may increase the number of hoses required so as to ensure
that hoses in sufficient number are available and accessible at all times,
having regard to the type of ship and the nature of trade in which the
ship is employed.
7.4.2 In cargo ships of less than 1,000 tons gross tonnage the number
of fire hoses to be provided shall be to the satisfaction of the
Administration.
8 Nozzles
8.1 For the purposes of this Chapter, standard nozzle sizes shall be
12 mm, 16 mm and 19 mm or as near thereto as possible. Larger diameter
nozzles may be permitted at the discretion of the Administration.
8.2 For accommodation and service spaces, a nozzle size greater than
12 mm need not be used.
8.3 For machinery spaces and exterior locations, the nozzle size shall
be such as to obtain the maximum discharge possible from two jets at the
pressure mentioned in paragraph 4 from the smallest pump, provided that a
nozzle size greater than 19 mm need not be used.
8.4 All nozzles shall be of an approved dual purpose type (i.e.
spray/jet type) incorporating a shut-off.
9 Location and arrangement of water pumps, etc., for other
fire-extinguishing systems
Pumps required for the provision of water for other fire-extinguishing
systems required by this Chapter, their sources of power and their
controls shall be installed outside the space or spaces protected by such
systems and shall be so arranged that a fire in the space or spaces
protected will not put any such system out of action.
Regulation 5 Fixed gas fire-extinguishing systems
1 General
1.1 The use of a fire-extinguishing medium which, in the opinion of
the Administration, either by itself or under expected conditions of use
gives off toxic gases in such quantities as to endanger persons shall not
be permitted.
1.2 The necessary pipes for conveying fire-extinguishing medium into
protected spaces shall be provided with control valves so marked as to
indicate clearly the spaces to which the pipes are led. Suitable provision
shall be made to prevent inadvertent admission of the medium to any space.
Where a cargo space fitted with a gas fire-extinguishing system is used as
a passenger space the gas connexion shall be blanked during such use.
1.3 The piping for the distribution of fire-extinguishing medium shall
be arranged and discharge nozzles so positioned that a uniform
distribution of medium is obtained.
1.4 Means shall be provided to close all openings which may admit air
to or allow gas to escape from a protected space.
1.5 Where the volume of free air contained in air receivers in any
space is such that, if released in such space in the event of fire, such
release of air within that space would seriously affect the efficiency of
the fixed fire-extinguishing system, the Administration shall require the
provision of an additional quantity of fire-extinguishing medium.
1.6 Means shall be provided for automatically giving audible warning
of the release of fire-extinguishing medium into any space in which
personnel normally work or to which they have access. The alarm shall
operate for a suitable period before the medium is released.
1.7 The means of control of any fixed gas fire-extinguishing systems
shall be readily accessible and simple to operate and shall be grouped
together in as few locations as possible at positions not likely to be cut
off by a fire in a protected space. At each location there shall be clear
instructions relating to the operation of the system having regard to the
safety of personnel.
1.8 Automatic release of fire-extinguishing medium shall not be
permitted, except as permitted by paragraph 3.3.5 and in respect of local
automatically operated units referred to in paragraphs 3.4 and 3.5.
1.9 Where the quantity of extinguishing medium is required to protect
more than one space, the quantity of medium available need not be more
than the largest quantity required for any one space so protected.
1.10 Except as otherwise permitted by paragraphs 3.3, 3.4 or 3.5
pressure containers required for the storage of fire-extinguishing medium,
other than steam, shall be located outside protected spaces in accordance
with paragraph 1.12.
1.11 Means shall be provided for the crew to safety check the quantity
of medium in the containers.
1.12 Containers for the storage of fire-extinguishing medium and
associated pressure components shall be designed to pressure codes of
practice to the satisfaction of the Administration having regard to their
locations and maximum ambient temperatures expected in service.
1.13 When the fire-extinguishing medium is stored outside a protected
space, it shall be stored in a room which shall be situated in a safe and
readily accessible position and shall be effectively ventilated to the
satisfaction of the Administration. Any entrance to such a storage room
shall preferably be from the open deck and in any case shall be
independent of the protected space. Access doors shall open outwards, and
bulkheads and decks including doors and other means of closing any opening
therein, which form the boundaries between such rooms and adjoining
enclosed spaces shall be gastight. For the purpose of the application of
the integrity tables in Regulations 26, 27, 44 and 58, such storage rooms
shall be treated as control stations.
1.14 Spare parts for the system shall be stored on board and be to the
satisfaction of the Administration.
2 Carbon dioxide systems
2.1 For cargo spaces the quantity of carbon dioxide available shall,
unless otherwise provided, be sufficient to give a minimum volume of free
gas equal to 30 per cent of the gross volume of the largest cargo space so
protected in the ship.
2.2 For machinery spaces the quantity of carbon dioxide carried shall
be sufficient to give a minimum quantity of free gas equal to the larger
of the following quantities, either:
.1 40 per cent of the gross volume of the largest machinery space
so protected, the volume to exclude that part of the casing above the
level at which the horizontal area of the casing is 40 per cent or less of
horizontal area of the space concerned taken midway between the tank top
and the lowest part of the casing; or
.2 35 per cent of the gross volume of the largest machinery space
protected, including the casing;
provided that the above-mentioned percentages may be reduced to 35 per
cent and 30 per cent respectively for cargo ships of less than 2,000 tons
gross tonnage; provided also that if two or more machinery spaces are not
entirely separate they shall be considered as forming one space.
2.3 For the purpose of this paragraph the volume of free carbon
dioxide shall be calculated
3 at 0.56 m /kg.
2.4 For machinery spaces the fixed piping system shall be such that 85
per cent of the gas can be discharged into the space within 2 minutes.
3 Halogenated hydrocarbon systems
3.1 The use of halogenated hydrocarbons as fire-extinguishing media is
only permitted in machinery spaces, pumprooms and in cargo spaces intended
solely for the carriage of vehicles which are not carrying any cargo.
3.2 When halogenated hydrocarbons are used as the fire-extinguishing
media in total flooding systems:
.1 The system shall be arranged for manual initiation of power
release only.
.2 If the charge of halogenated hydrocarbon is required to supply
more than one space, the arrangements for its storage and release shall
be such that compliance with paragraphs 3.2.9 or 3.2.10 respectively, is
obtained.
.3 Means shall be provided for automatically stopping all
ventilation fans serving the protected space before the medium is
released.
.4 Means shall be provided to manually close all dampers in the
ventilation system serving a protected space.
.5 The discharge arrangements shall be so designed that the
minimum quantity of medium required for cargo spaces or machinery spaces
in paragraphs 3.2.9 or 3. 2.10 respectively can be substantially
discharged in a nominal 20 seconds or less based on the discharge of the
liquid phase.
.6 The system shall be designed to operate within a temperature
range to the satisfaction of the Administration.
.7 The discharge shall not endanger personnel engaged on
maintenance of equipment or using the normal access ladders and escapes
serving the space.
.8 Means shall be provided for the crew to safely check the
pressure within containers.
.9 The quantity of extinguishing medium for cargo spaces intended
solely for the carriage of vehicles which are not carrying any cargo shall
be calculated in accordance with table 5.1. This quantity shall be based
on the gross volume of the protected space. In respect of Halon 1301 and
1211, the quantity shall be calculated on a volumetric ratio basis, and in
respect of Halon 2402 on a mass per unit volume basis. TABLE 5.1
|---------------
| Halon | Minimum | Maximum |
|----|-------|-------|
| 1301 | 5 per cent | 7 per cent |
| 1211 | 5 per cent | 5.5 per cent |
| 3 | 3 |
| 2402 | 0.23 kg/m | 0.30 kg/m |
|---------------
.10 The quantity of extinguishing media for machinery spaces shall
be calculated in accordance with table 5.2. This quantity shall be based
on the gross volume of the space in respect of the minimum concentration
and the net volume of the space in respect of the maximum concentration,
including the casing. In respect of Halon 1301 and 1211, the quantity
shall be calculated on a volumetric ratio basis, and in respect of Halon
2402 on a mass per unit volume basis.
TABLE 5.2
|----------------
| Halon | Minimum | Maximum |
|----|-------|-------|
| 1301 | 4.25 per cent | 7 per cent |
| 1211 | 4.25 per cent | 5.5 per cent |
| 2402 | 0.20 kg/cubic m | 0.30 kg/cubic m |
----------------
.11 For the purpose of paragraphs 3.2.9 and 3.2.10, the volume of
Halon 1301 shall
3 be calculated at 0.16 m /kg and the volume of
Halon 1211 shall be calculated at 0.
3 14 m /kg.
3.3 Only Halon 1301 may be stored within a protected machinery space.
Containers shall be individually distributed throughout that space and the
following requirements shall be complied with:
.1 A manually initiated power release, located outside the
protected space, shall be provided. Duplicate sources of power shall be
provided for this release and shall be located outside the protected space
and be immediately available except that for machinery spaces, one of the
sources of power may be located inside the protected space.
.2 Electrical power circuits connecting the containers shall
monitored for fault conditions and loss of power. Visual and audible
alarms shall be provided to indicate this.
.3 Pneumatic or hydraulic power circuits connecting the containers
shall be duplicated. The sources of pneumatic or hydraulic pressure shall
be monitored for loss of pressure. Visual and audible alarms shall be
provided to indicate this.
.4 Within the protected space, electrical circuits essential for
the release of the system shall be heat resistant e.g. mineral insulated
cable or equivalent. Piping systems essential for the release of systems
designed to be operated hydraulically or pneumatically shall be of steel
or other equivalent heat-resisting material to the satisfaction of the
Administration.
.5 Each pressure container shall be fitted with an automatic
over-pressure release device which, in the event of the container being
exposed to the effects of fire and the system not being operated, will
safely vent the contents of the container into the protected space.
.6 The arrangement of containers and the electrical circuits and
piping essential for the release of any system shall be such that in the
event of damage to any one power release line through fire or explosion in
a protected space, i.e. a single fault concept, at least two-thirds of
the fire-extinguishing charge required by paragraphs 3.2.9 or 3.2.10 for
that space can still be discharged having regard to the requirement for
uniform distribution of medium throughout the space. The arrangements in
respect of systems for spaces requiring only one or two containers shall
be to the satisfaction of the Administration.
.7 Nor more than two discharge nozzles shall be fitted to any
pressure container and the maximum quantity of agent in each container
shall be to the satisfaction of the Administration having regard to the
requirement for uniform distribution of medium throughout the space.
.8 The containers shall be monitored for decrease in pressure due
to leakage and discharge. Visual and audible alarms in the protected area
and on the navigating bridge or in the space where the fire control
equipment is centralized shall be provided to indicate this condition,
except that for cargo spaces, alarms are only required on the navigating
bridge or the space where the fire control equipment is centralized.
3.4 Local automatically operated fixed fire-extinguishing units
containing Halon 1301 or 1211, fitted in enclosed areas of high fire risk
within machinery spaces, in addition to, and independent of, any required
fixed fire-extinguishing system may be accepted subject to compliance with
the following:
.1 The space in which such additional local protection is provided
shall preferably be on one working level and on the same level as the
access. At the discretion of Administration more than one working level
may be permitted subject to an access being provided on each level.
.2 The size of the space and arrangements of accesses thereto and
machinery therein, shall be such that escape from anywhere in the space
can be effected in not more than 10 seconds.
.3 The operation of any unit shall be signalled both visually and
audibly outside each access to the machinery space and at the navigating
bridge or in the space where the fire control equipment is centralized.
.4 A notice indicating that the space contains one or more
automatically operated fire-extinguishing units and stating which medium
is used, shall be displayed outside each access thereto.
.5 Discharge nozzles shall be so positioned that the discharge
does not endanger personnel using the normal access ladders and escapes
serving the compartment. Provision shall also be made to protect personnel
engaged in maintenance of machinery from inadvertent discharge of the
medium.
.6 The fire-extinguishing units shall be designed to operate
within a temperature range to the satisfaction of the Administration.
.7 Means shall be provided for the crew to safely check the
pressure within the containers.
.8 The total quantity of extinguishing medium provided in the
local automatically operated units shall be such that a concentration of 7
per cent in respect of Halon 1301 and 5.5 per cent in respect of Halon
1211 at 20¡æ based on the net volume of the enclosed space is not
exceeded. This requirement applies when either a local automatically
operated unit or a fixed system fitted in compliance with paragraph 3.2
has operated, but not when both have operated. The volume of Halon 1301
shall be calculated at 0.16 cubic m /kg and the volume of Halon 1211 shall
be calculated at 0.14 cubic m /kg.
.9 The time of discharge of a unit, based on the discharge of the
liquid phase, shall be 10 seconds or less.
.10 The arrangement of local automatically operated
fire-extinguishing units shall be such that their release does not result
in loss of electrical power or reduction of the manoeuvrability of the
ship.
3.5 Automatically operated fire-extinguishing units, as described in
paragraph 3.4, fitted in machinery spaces over equipment having a high
fire risk, in addition to and independent of any required fixed
fire-extinguishing system, may be accepted subject to compliance with
paragraphs 3.4.3 to 3.4.6, 3.4.9 and 3.4.10 and with the following:
.1 The quantity of medium provided in local automatically operated
units shall be such that a vapour in air concentration not greater than
1.25 per cent at 20¡æ based on the gross volume of the machinery space is
obtained in the event of their simultaneous operation.
.2 The volume of Halon 1301 shall be calculated at 0.16 cubic m
/kg and the volume of Halon 1211 shall be calculated at 0.14 cubic m /kg.
4 Steam systems
In general, the Administration shall not permit the use of steam as a
fire-extinguishing medium in fixed fire-extinguishing systems. Where the
use of steam is permitted by the Administration it shall be used only in
restricted areas as an addition to the required fire-extinguishing medium
and with the proviso that the boiler or boilers available for supplying
steam
3 shall have an evaporation of at least 1.0 kg of steam per hour for each
0.75 m of the gross volume of the largest space so protected. In addition
to complying with the foregoing requirements the systems in all respects
shall be as determined by, and to the satisfaction of, the Administration.
5 Other gas systems
5.1 Where gas other than carbon dioxide or halogenated hydrocarbons,
or steam as permitted by paragraph 4 is produced on the ship and is used
as a fire-extinguishing medium, it shall be a gaseous product of fuel
combustion in which the oxygen content, the carbon monoxide content, the
corrosive elements and any solid combustible elements have been reduced to
a permissible minimum.
5.2 Where such gas is used as the fire-extinguishing medium in a fixed
fire-extinguishing system for the protection of machinery spaces it shall
afford protection equivalent to that provided by a fixed system using
carbon dioxide as the medium.
5.3 Where such gas is used as a fire-extinguishing medium in a fixed
fire-extinguishing system for the protection of cargo spaces, a sufficient
quantity of such gas shall be available to supply hourly a volume of free
gas at least equal to 25 per cent of the gross volume of the largest space
protected in this way for a period of 72 hours.
Regulation 6 Fire extinguishers
1 All fire extinguishers shall be of approved types and designs.
1.1 The capacity of required portable fluid extinguishers shall be not
more than 13.5 l and not less than 9 l. Other extinguishers shall be at
least as portable as the 13.5 l fluid extinguisher and shall have a
fire-extinguishing capability at least equivalent to that of a 9 l fluid
extinguisher.
1.2 The Administration shall determine the equivalents of fire
extinguishers.
2 Spare charges shall be provided in accordance with requirements to
be specified by the Administration.
3 Fire extinguishers containing an extinguishing medium which, in the
opinion of the Administration, either by itself or under expected
conditions of use gives off toxic gases in such quantities as to endanger
persons shall not be permitted.
4 A portable foam applicator unit shall consist of an air-foam nozzle
of an inductor type capable of being connected to the fire main by a fire
hose, together with a portable tank containing at least 20 l of
foam-making liquid and one spare tank. The nozzle shall be capable of
3 producing effective foam suitable for extinguishing an oil fire, at the
rate of at least 1.5 m / minute.
5 Fire extinguishers shall be periodically examined and subjected to
such tests as the Administration may require.
6 One of the portable fire extinguishers intended for use in any space
shall be stowed near the entrance to that space.
7 Accommodation spaces, service spaces and control stations shall be
provided with portable fire extinguishers of appropriate types and in
sufficient number to the satisfaction of the Administration. Ships of
1,000 tons gross tonnage and upwards shall carry at least five portable
fire extinguishers.
Regulation 7 Fire-extinguishing arrangements in machinery spaces
1 Spaces containing oil-fired boilers or oil fuel units
1.1 Machinery spaces of category A containing oil-fired boilers or oil
fuel units shall be provided with any one of the following fixed
fire-extinguishing systems:
.1 a gas system complying with the provisions of Regulation 5;
.2 a high expansion foam system complying with the provisions of
Regulation 9;
.3 a pressure water-spraying system complying with the provisions
of Regulation 10.
In each case if the engine and boiler rooms are not entirely separate,
or if fuel oil can drain from the boiler room into the engine room, the
combined engine and boiler rooms shall be considered as one compartment.
1.2 There shall be in each boiler room at least one set of portable
air-foam equipment complying with the provisions of Regulation 6.4.
1.3 There shall be at least two portable foam extinguishers or
equivalent in each firing space in each boiler room and in each space in
which a part of the oil fuel installation is situated. These shall be not
less than one approved foam-type extinguisher of at least 135 l capacity
or equivalent in each boiler room. These extinguishers shall be provided
with hoses on reels suitable for reaching any part of the boiler room. In
the case of domestic boilers of less than 175 kW in cargo ships the
Administration may consider relaxing the requirements of this paragraph.
1.4 In each firing space there shall be a receptacle containing sand,
sawdust impregnated with soda, or other approved dry material in such
quantity as may be required by the Administration. An approved portable
extinguisher may be substituted as an alternative.
2 Spaces containing internal combustion machinery
Machinery spaces of category A containing internal combustion
machinery shall be provided with:
.1 One of the fire-extinguishing systems required by paragraph
1.1.
.2 At least one set of portable air-foam equipment complying with
the provisions of Regulation 6.4.
.3 In each such space approved foam type fire extinguishers, each
of at least 45 l capacity or equivalent, sufficient in number to enable
foam or its equivalent to be directed on to any part of the fuel and
lubricating oil pressure systems, gearing and other fire hazards. In
addition, there shall be provided a sufficient number of portable foam
extinguishers or equivalent which shall be so located that no point in the
space is more than 10 m walking distance from an extinguisher and that
there are at least two such extinguishers in each such space. For smaller
spaces of cargo ships the Administration may consider relaxing this
requirement.
3 Spaces containing steam turbines or enclosed steam engines
In spaces containing steam turbines or enclosed steam engines used
either for main propulsion or for other purposes when such machinery has
in the aggregate a total power output of not less than 375 kW there shall
be provided:
.1 Approved foam fire extinguishers each of at least 45 l capacity
or equivalent sufficient in number to enable foam or its equivalent to be
directed on to any part of the pressure lubrication system, on to any part
of the casings enclosing pressure lubricated parts of the turbines,
engines or associated gearing, and any other fire hazards. However, such
extinguishers shall not be required if protection at least equivalent to
that required by this sub-paragraph is provided in such spaces by a fixed
fire-extinguishing system fitted in compliance with paragraph 1.1.
.2 A sufficient number of portable foam extinguishers or
equivalent which shall be so located that no point in the space is more
than 10 m walking distance from an extinguisher and that there are at
least two such extinguishers in each such space, except that such
extinguishers shall not be required in addition to any provided in
compliance with paragraph 1.3.
.3 One of the fire-extinguishing systems required by paragraph
1.1, where such spaces are periodically unattended.
4 Fire-extinguishing appliances in other machinery spaces
Where, in the opinion of the Administration, a fire hazard exists in
any machinery space for which no specific provisions for
fire-extinguishing appliances are prescribed in paragraphs 1, 2 and 3,
there shall be provided in, or adjacent to, that space such a number of
approved portable fire extinguishers or other means of fire extinction as
the Administration may deem sufficient.
5 Fixed fire-extinguishing systems not required by this Chapter
Where a fixed fire-extinguishing system not required by this Chapter
is installed, such a system shall be to the satisfaction of the
Administration.
6 Machinery spaces of category A in passenger ships
In passenger ships carrying more than 36 passengers each machinery
space of category A shall be provided with at least two suitable water fog
applicators. *
[* A water fog applicator might consist of a metal "L" -shaped pipe,
the long limb being about 2 m in length capable of being fitted to a fire
hose and the short limb being about 250 mm in length fitted with a fixed
water fog nozzle or capable of being fitted with a water spray nozzle.]
Regulation 8 Fixed low-expansion foam fire-extinguishing systemsin machinery spaces
1 Where in any machinery space a fixed low-expansion foam
fire-extinguishing system is fitted in addition to the requirements of
Regulation 7, such system shall be capable of discharging through fixed
discharge outlets in not more than five minutes a quantity of foam
sufficient to cover to a depth of 150 mm the largest single area over
which oil fuel is liable to spread. The system shall be capable of
generating foam suitable for extinguishing oil fires. Means shall be
provided for effective distribution of the foam through a permanent system
of piping and control valves or cocks to suitable discharge outlets, and
for the foam to be effectively directed by fixed sprayers on other main
fire hazards in the protected space. The expansion ratio of the foam shall
not exceed 12 to 1.
2 The means of control of any such systems shall be readily accessible
and simple to operate and shall be grouped together in as few locations as
possible at positions not likely to be cut off by a fire in the protected
space.
Regulation 9 Fixed high-expansion foam fire-extinguishing systemsin machinery spaces
1.1 Any required fixed high-expansion foam system in machinery spaces
shall be capable of rapidly discharging through fixed discharge outlets a
quantity of foam sufficient to fill the greatest space to be protected at
a rate of at least 1 m in depth per minute. The quantity of foam-forming
liquid available shall be sufficient to produce a volume of foam equal to
five times the volume of the largest space to be protected. The expansion
ratio of the foam shall not exceed 1,000 to 1.
1.2 The Administration may permit alternative arrangements and
discharge rates provided that it is satisfied that equivalent protection
is achieved.
2 Supply ducts for delivering foam, air intakes to the foam generator
and the number of foam-producing units shall in the opinion of the
Administration be such as will provide effective foam production and
distribution.
3 The arrangement of the foam generator delivery ducting shall be such
that a fire in the protected space will not affect the foam generating
equipment.
4 The foam generator, its sources of power supply, foam-forming liquid
and means of controlling the system shall be readily accessible and simple
to operate and shall be grouped in as few locations as possible at
positions not like to be cut off by a fire in the protected space.
Regulation 10 Fixed pressure water-spraying fire-extinguishingsystems in machinery spaces
1 Any required fixed pressure water-spraying fire-extinguishing system
in machinery spaces shall be provided with spraying nozzles of an approved
type.
2 The number and arrangement of the nozzles shall be to the
satisfaction of the Administration and shall be such as to ensure an
effective average distribution of water of at least 5 l/
3 m per minute in the spaces to be protected. Where increased
application rates are considered necessary, these shall be to the
satisfaction of the Administration. Nozzles shall be fitted above bilges,
tank tops and other areas over which oil fuel is liable to spread and
also above other specific fire hazards in the machinery spaces.
3 The system may be divided into sections, the distribution valves of
which shall be operated from easily accessible positions outside the
spaces to be protected and will not be readily cut off by a fire in the
protected space.
4 The system shall be kept charged at the necessary pressure and the
pump supplying the water for the system shall be put automatically into
action by a pressure drop in the system.
5 The pump shall be capable of simultaneously supplying at the
necessary pressure all sections of the system in any one compartment to be
protected. The pump and its controls shall be installed outside the space
or spaces to be protected. It shall not be possible for a fire in the
space or spaces protected by the water-spraying system to put the system
out of action.
6 The pump may be driven by independent internal combustion machinery
but, if it is dependent upon power being supplied from the emergency
generator fitted in compliance with the provisions of Regulation II-1/44
or Regulation II-1/45, as appropriate, that generator shall be so arranged
as to start automatically in case of main power failure so that power for
the pump required by paragraph 5 is immediately available. When the pump
is driven by independent internal combustion machinery it shall be so
situated that a fire in the protected space will not affect the air supply
to the machinery.
7 Precautions shall be taken to prevent the nozzles from becoming
clogged by impurities in the water or corrosion of piping, nozzles, valves
and pump.
Regulation 11 Special arrangements in machinery spaces
1 The provisions of this Regulation shall apply to machinery spaces of
category A and, where the Administration considers it desirable, to other
machinery spaces.
2.1 The number of skylights, doors, ventilators, openings in funnels
to permit exhaust ventilation and other openings to machinery spaces shall
be reduced to a minimum consistent with the needs of ventilation and the
proper and safe working of the ship.
2.2 Skylights shall be of steel and shall not contain glass panels.
Suitable arrangements shall be made to permit the release of smoke in the
event of fire, from the space to be protected.
2.3 In passenger ships, doors other than power-operated watertight
doors, shall be so arranged that positive closure is assured in case of
fire in the space, by power-operated closing arrangements or by the
provision of self-closing doors capable of closing against an inclination
of 3.5 ¡ã opposing closure and having a fail-safe hook-back facility,
provided with a remotely operated release device.
3 Windows shall not be fitted in machinery space boundaries. This does
not preclude the use of glass in control rooms within the machinery
spaces.
4 Means of control shall be provided for:
.1 opening and closure of skylights, closure of openings in
funnels which normally allow exhaust ventilation, and closure of
ventilator dampers;
.2 permitting the release of smoke;
.3 closing power-operated doors or actuating release mechanism on
doors other than power-operated watertight doors;
.4 stopping ventilating fans; and
.5 stopping forced and induced draught fans, oil fuel transfer
pumps, oil fuel unit pumps and other similar fuel pumps.
5 The controls required in paragraph 4 and in Regulation 15.2.5 shall
be located outside the space concerned, where they will not be cut off in
the event of fire in the space they serve. In passenger ships such
controls and the controls for any required fire-extinguishing system shall
be situated at one control position or grouped in as few positions as
possible to the satisfaction of the Administration. Such positions shall
have a safe access from the open deck.
6 When access to any machinery space of category A is provided at a
low level from an adjacent shaft tunnel, there shall be provided in the
shaft tunnel, near the watertight door, a light steel fire-screen door
operable from each side.
7 For periodically unattended machinery spaces in cargo ships, the
Administration shall give special consideration to maintaining fire
integrity of the machinery spaces, the location and centralization of the
fire-extinguishing system controls, the required shut-down arrangements
(e.g. ventilation, fuel pumps, etc.) and may require additional
fire-extinguishing appliances and other fire-fighting equipment and
breathing apparatus. In passenger ships these requirements shall be at
least equivalent to those of machinery spaces normally attended.
8 An approved automatic fire detection and alarm system complying with
the provisions of Regulation 14 shall be fitted in any machinery space:
.1 where the installation of automatic and remote control systems
and equipment has been approved in lieu of continuous manning of the
space; and
.2 where the main propulsion and associated machinery including
sources of main electrical supply are provided with various degrees of
automatic or remote control and are under continuous manned supervision
from a control room.
Regulation 12 Automatic sprinkler, fire detection and fire alarmsystems
1.1 Any required automatic sprinkler, fire detection and fire alarm
system shall be capable of immediate operation at all times and no action
by the crew shall be necessary to set it in operation. It shall be of the
wet pipe type but small exposed sections may be of the dry pipe type where
in the opinion of the Administration this is a necessary precaution. Any
parts of the system which may be subjected to freezing temperatures in
service shall be suitably protected against freezing. It shall be kept
charged at the necessary pressure and shall have provision for a
continuous supply of water as required in this Regulation.
1.2 Each section of sprinklers shall include means for giving a visual
and audible alarm signal automatically at one or more indicating units
whenever any sprinkler comes into operation. Such alarm systems shall be
such as to indicate if any fault occurs in the system.
1.2.1 In passenger ships such units shall give an indication of any
fire and its location in any space served by the system and shall be
centralized on the navigating bridge or in the main fire control station,
which shall be so manned or equipped as to ensure that any alarm from the
system is immediately received by a responsible member of the crew.
1.2.2 In cargo ships such units shall indicate in which section served
by the system fire has occurred and shall be centralized on the navigating
bridge and in addition, visible and audible alarms from the unit shall be
placed in a position other than on the navigating bridge, so as to ensure
that the indication of fire is immediately received by the crew.
2.1 Sprinklers shall be grouped into separate sections, each of which
shall contain not more than 200 sprinklers. In passenger ships any section
of sprinklers shall not serve more than two decks and shall not be
situated in more than one main vertical zone. However, the Administration
may permit such a section of sprinklers to serve more than two decks or be
situated in more than one main vertical zone, if it is satisfied that the
protection of the ship against fire will not thereby be reduced.
2.2 Each section of sprinklers shall be capable of being isolated by
one stop valve only. The stop valve in each section shall be readily
accessible and its location shall be clearly and permanently indicated.
Means shall be provided to prevent the operation of the stop valves by any
unauthorized person.
2.3 A gauge indicating the pressure in the system shall be provided at
each section stop valve and at a central station.
2.4 The sprinklers shall be resistant to corrosion by marine
atmosphere. In accommodation and service spaces the sprinklers shall come
into operation within the temperature range from 68¡ã to 79¡æ, except that
in locations such as drying rooms, where high ambient temperatures might
be expected, the operating temperature may be increased by not more than
30¡æ above the maximum deckhead temperature.
2.5 A list or plan shall be displayed at each indicating unit showing
the spaces covered and the location of the zone in respect of each
section. Suitable instructions for testing and maintenance shall be
available.
3 Sprinklers shall be placed in an overhead position and spaced in a
suitable pattern to maintain anaverage application rate of not less than
5 l/ square m per minute over the nominal area covered by the sprinklers.
However, the Administration may permit the use of sprinklers providing
such an alternative amount of water suitably distributed as has been
shown to the satisfaction of the Administration to be not less effective.
4.1 A pressure tank having a volume equal to at least twice that of
the charge of water specified in this sub-paragraph shall be provided. The
tank shall contain a standing charge of fresh water, equivalent to the
amount of water which would be discharged in one minute by the pump
referred to in paragraph 5.2, and the arrangements shall provide for
maintaining an air pressure in the tank such as to ensure that where the
standing charge of fresh water in the tank has been used the pressure will
be not less than the working pressure of the sprinkler, plus the pressure
exerted by a head of water measured from the bottom of the tank to the
highest sprinkler in the system. Suitable means of replenishing the air
under pressure and of replenishing the fresh water charge in the tank
shall be provided. A glass gauge shall be provided to indicate the correct
level of the water in the tank.
4.2 Means shall be provided to prevent the passage of sea-water into
the tank.
5.1 An independent power pump shall be provided solely for the purpose
of continuing automatically the discharge of water from the sprinklers.
The pump shall be brought into action automatically by the pressure drop
in the system before the standing fresh water charge in the pressure tank
is completely exhausted.
5.2 The pump and the piping system shall be capable of maintaining the
necessary pressure at the level of the highest sprinkler to ensure a
continuous output of water sufficient for the
2 simultaneous coverage of
a minimum area of 280 m at the application rate specified in paragraph 3.
5.3 The pump shall have fitted on the delivery side a test valve with
a short open-ended discharge pipe. The effective area through the valve
and pipe shall be adequate to permit the release of the required pump
output while maintaining the pressure in the system specified in paragraph
4.1.
5.4 The sea inlet to the pump shall wherever possible be in the space
containing the pump and shall be so arranged that when the ship is afloat
it will not be necessary to shut off the supply of sea-water to the pump
for any purpose other than the inspection or repair of the pump.
6 The sprinkler pump and tank shall be situated in a position
reasonably remote from any machinery space of category A and shall not be
situated in any space required to be protected by the sprinkler system.
7.1 In passenger ships there shall be not less than two sources of
power supply for the seawater pump and automatic alarm and detection
system. Where the sources of power for the pump are electrical, these
shall be a main generator and an emergency source of power. One supply for
the pump shall be taken from the main switchboard, and one from the
emergency switchboard by separate feeders reserved solely for that
purpose. The feeders shall be so arranged as to avoid galleys, machinery
spaces and other enclosed space of high risk except in so far as it is
necessary to reach the appropriate switchboards, and shall be run to an
automatic change-over switch situated near the sprinkler pump. This switch
shall permit the supply of power from the main switchboard so long as a
supply is available therefrom, and be so designed that upon failure of
that supply it will automatically change over to the supply from the
emergency switchboard. The switches on the main switchboard and the
emergency switchboard shall be clearly labelled and normally kept closed.
No other switch shall be permitted in the feeders concerned. One of the
sources of power supply for the alarm and detection system shall be an
emergency source. Where one of the sources of power for the pump is an
internal combustion engine it shall, in addition to complying with the
provisions of paragraph 6, be so situated that a fire in any protected
space will not affect the air supply to the machinery.
7.2 In cargo ships there shall not be less than two sources of power
supply for the sea-water pump and automatic alarm and detection system. If
the pump is electrically driven it shall be connected to the main source
of electrical power, which shall be capable of being supplied by at least
two generators. The feeders shall be so arranged as to avoid galleys,
machinery spaces and other enclosed spaces of high fire risk except in so
far as it is necessary to reach the appropriate switchboards. One of the
sources of power supply for the alarm and detection system shall be an
emergency source. Where one of the sources of power for the pump is an
internal combustion engine it shall, in addition to complying with the
provisions of paragraph 6, be so situated that a fire in any protected
space will not affect the air supply to the machinery.
8 The sprinkler system shall have a connexion from the ship's fire
main by way of a lockable screw-down non-return valve at the connexion
which will prevent a backflow from the sprinkler system to the fire main.
9.1 A test valve shall be provided for testing the automatic alarm for
each section of sprinklers by a discharge of water equivalent to the
operation of one sprinkler. The test valve for each section shall be
situated near the stop valve for that section.
9.2 Means shall be provided for testing the automatic operation of the
pump on reduction of pressure in the system.
9.3 Switches shall be provided at one of the indicating positions
referred to in paragraph 1. 2 which will enable the alarm and the
indicators for each section of sprinklers to be tested.
10 Spare sprinkler heads shall be provided for each section of
sprinklers to the satisfaction of the Administration.
Regulation 13 Fixed fire detection and fire alarm systems
1 General requirements
1.1 Any required fixed fire detection and fire alarm system with
manually operated call points shall be capable of immediate operation at
all times.
1.2 Power supplies and electric circuits necessary for the operation
of the system shall be monitored for loss of power of fault conditions as
appropriate. Occurrence of a fault condition shall initiate a visual and
audible fault signal at the control panel which shall be distinct from a
fire signal.
1.3 There shall be not less than two sources of power supply for the
electrical equipment used in the operation of the fire detection and fire
alarm system, one of which shall be an emergency source. The supply shall
be provided by separate feeders reserved solely for that purpose. Such
feeders shall run to an automatic change-over switch situated in or
adjacent to the control panel for the fire detection system.
1.4 Detectors and manually operated call points shall be grouped into
sections. The activation of any detector or manually operated call point
shall initiate a visual and audible fire signal at the control panel and
indicating units. If the signals have not received attention within two
minutes an audible alarm shall be automatically sounded throughout the
crew accommodation and service spaces, control stations and machinery
spaces of category A. This alarm sounder system need not be an integral
part of the detection system.
1.5 The control panel shall be located on the navigating bridge or in
the main fire control station.
1.6 Indicating units shall denote the section in which a detector or
manually operated call point has operated. At least one unit shall be so
located that it is easily accessible to responsible members of the crew at
all times, when at sea or in port except when the ship is out of service.
One indicating unit shall be located on the navigating bridge if the
control panel is located in the main fire control station.
7 Clear information shall be displayed on or adjacent to each
indicating unit about the spaces covered and the location of the sections.
1.8 No section covering more than one deck within accommodation,
service and control stations shall normally be permitted except a section
which covers an enclosed stairway. In order to avoid delay in identifying
the source of fire, the number of enclosed spaces included in each section
shall be limited as determined by the Administration. In no case shall
more than fifty enclosed spaces be permitted in any section.
1.9 In passenger ships a section of detectors shall not serve spaces
on both sides of the ship nor on more than one deck and neither shall it
be situated in more than one main vertical zone except that the
Administration, if it is satisfied that the protection of the ship against
fire will not thereby be reduced, may permit such a section of detectors
to serve both sides of the ship and more than one deck.
1.10 A section of fire detectors which covers a control station, a
service space or an accommodation space shall not include a machinery
space of category A.
1.11 Detectors shall be operated by heat, smoke or other products of
combustion, flame, or any combination of these factors. Detectors
operated by other factors indicative of incipient fires may be considered
by the Administration provided that they are no less sensitive than such
detectors. Flame detectors shall only be used in addition to smoke or heat
detectors.
1.12 Suitable instructions and components spares for testing and
maintenance shall be provided.
1.13 The function of the detection system shall be periodically tested
to the satisfaction of the Administration by means of equipment producing
hot air at the appropriate temperature, or smoke or aerosol particles
having the appropriate range of density or particle size, or other
phenomena associated with incipient fires to which the detector is
designed to respond. All detectors shall be of a type such that they can
be tested for correct operation and restored to normal surveillance
without the renewal of any component.
1.14 The fire detection system shall not be used for any other
purpose, except that closing of fire doors and similar functions may be
permitted at the control panel.
2 Installation requirements
2.1 Manual call points shall be installed throughout the accommodation
spaces, service spaces and control stations. One manual call point shall
be located at each exit. Manual call points shall be readily accessible in
the corridors of each deck such that no part of the corridor is more than
20 m from a manual call point.
2.2 Smoke detectors shall be installed in all stairways, corridors and
escape routes within accommodation spaces. Consideration shall be given to
the installation of special purpose smoke detectors within ventilation
ducting.
2.3 Where a fixed fire detection and fire alarm system is required for
the protection of spaces other than those specified in paragraph 2.2, at
least one detector complying with paragraph 1.11 shall be installed in
each such space.
2.4 Detectors shall be located for optimum performance. Positions near
beams and ventilation ducts or other positions where patterns of air flow
could adversely affect performance and positions where impact or physical
damage is likely shall be avoided. In general, detectors which are located
on the overhead shall be a minimum distance of 0.5 m away from bulkheads.
2.5 The maximum spacing of detectors shall be in accordance with the
table below:
|-----------------------
| Type of | Maximum floor area | Maximum distance apart | Maximum distance away |
| detector | per detector | between centres | from bulkheads |
|----|------|--------|-------|
| 2 | |
| Heat | 37 m | 9 m | 4.5 m |
|----|------|--------|-------|
| 2 | |
| Smoke | 74 m | 11 m | 5.5 m |
|-----------------------
The Administration may require or permit other spacings based upon
test data which demonstrate the characteristics of the detectors.
2.6 Electrical wiring which forms part of the system shall be so
arranged as to avoid galleys, machinery spaces of category A, and other
enclosed spaces of high fire risk except where it is necessary to provide
for fire detection or fire alarm in such spaces or to connect to the
appropriate power supply.
3 Design requirements
3.1 The system and equipment shall be suitably designed to withstand
supply voltage variation and transients, ambient temperature changes,
vibration, humidity, shock, impact and corrosion normally encountered in
ships.
3.2 Smoke detectors required by paragraph 2.2 shall be certified to
operate before the smoke density exceeds 12.5 per cent obscuration per
metre, but not until the smoke density exceeds 2 per cent obscuration per
metre. Smoke detectors to be installed in other spaces shall operate
within sensitivity limits to the satisfaction of the Administration having
regard to the avoidance of detector insensitivity or oversensitivity.
3.3 Heat detectors shall be certified to operate before the
temperature exceeds 78¡æ but not until the temperature exceeds 54 ¡æ, when
the temperature is raised to those limits at a rate less than 1¡æ per
minute. At higher rates of temperature rise, the heat detector shall
operate within temperature limits to the satisfaction of the
Administration having regard to the avoidance of detector insensitivity or
oversensitivity.
3.4 At the discretion of the Administration, the permissible
temperature of operation of heat detectors may be increased to 30¡æ above
the maximum deckhead temperature in drying rooms and similar spaces of a
normal high ambient temperature.
Regulation 14 Fixed fire detection and fire alarm systems for pe-riodically unattended machinery spaces
1 A fixed fire detection and fire alarm system in accordance with the
relevant provisions of Regulation 13 shall be installed in periodically
unattended machinery spaces.
2 This fire detection system shall be so designed and the detectors so
positioned as to detect rapidly the onset of fire in any part of those
spaces an d under any normal conditions of operation of the machinery and
variations of ventilation as required by the possible range of ambient
temperature. Except in spaces of restricted height and where their use is
specially appropriate, detection systems using only thermal detector shall
not be permitted. The detection system shall initiate audible and visual
alarms distinct in both respects from the alarms of any other system not
indicating fire, in sufficient places to ensure that the alarms are heard
and observed on the navigating bridge and by a responsible engineer
officer. When the navigating bridge is unmanned the alarm shall sound in a
place where a responsible member of the crew is on duty.
3 After installation the system shall be tested under varying
conditions of engine operation and ventilation.
Regulation 15 Arrangements for oil fuel, lubricating oil and otherflammable oils
1 Limitations in the use of oil as fuel
The following limitations shall apply to the use of oil as fuel:
.1 Except as otherwise permitted by this paragraph, no oil fuel
with a flashpoint of less than 60 ¡æ shall be used.
.2 In emergency generators oil fuel with a flashpoint of not less
than 43 ¡æ may be used.
.3 Subject to such additional precautions as it may consider
necessary and on condition that the ambient temperature of the space in
which such oil fuel is stored or used shall not be allowed to rise to
within 10¡æ below the flashpoint of the oil fuel, the Administration may
permit the general use of oil fuel having a flashpoint of less than 60¡æ
but not less than 43¡æ.
.4 In cargo ships the use of fuel having a lower flashpoint than
otherwise specified in this paragraph, for example crude oil, may be
permitted provided that such fuel is not stored in any machinery space and
subject to the approval by the Administration of the complete
installation.
The flashpoint of oils shall be determined by an approved closed cup
method.
2 Oil fuel arrangements
In a ship in which oil fuel is used, the arrangements for the storage,
distribution and utilization of the oil fuel shall be such as to ensure
the safety of the ship and persons on board and shall at least comply with
the following provisions:
.1 As far as practicable, parts of the oil fuel system containing
heated oil under pressureexceeding 0.18 N/square mm shall not be placed
in a concealed position such that defects and leakage cannot readily be
observed .The machinery spaces in way of such parts of the oil fuel system
shall be adequately illuminated.
.2 The ventilation of machinery spaces shall be sufficient under
all normal conditions to prevent accumulation of oil vapour.
.3 As far as practicable, oil fuel tanks shall be part of the
ship's structure and shall be located outside machinery spaces of category
A. Where oil fuel tanks, other than double bottom tanks, are necessarily
located adjacent to or within machinery spaces of category A, at least one
of their vertical sides shall be contiguous to the machinery space
boundaries, and shall preferably have a common boundary with the double
bottom tanks, and the area of the tank boundary common with the machinery
spaces shall be kept to a minimum. Where such tanks are situated within
the boundaries of machinery spaces of category A they shall not contain
oil fuel having a flashpoint of less than 60¡æ. In general the use of free
standing oil fuel tanks shall be avoided. When such tanks are employed
their use shall be prohibited in category A machinery spaces on passenger
ships. Where permitted, they shall be placed in an oil-tight spill tray of
ample size having a suitable drain pipe leading to a suitably sized spill
oil tank.
.4 No oil fuel tank shall be situated where spillage or leakage
therefrom can constitute a hazard by falling on heated surfaces.
Precautions shall be taken to prevent any oil that may escape under
pressure from any pump, filter or heater from coming into contact with
heated surfaces.
.5 Every oil fuel pipe, which, if damaged, would allow oil to
escape from a storage, settling or daily service tank situated above the
double bottom shall be fitted with a cock or valve directly on the tank
capable of being closed from a safe position outside the space concerned
in the event of a fire occurring in the space in which such tanks are
situated. In the special case of deep tanks situated in any shaft or pipe
tunnel or similar space, valves on the tank shall be fitted but control in
the event of fire may be effected by means of an additional valve on the
pipe or pipes outside the tunnel or similar space. If such additional
valve is fitted in the machinery space it shall be operated from a
position outside this space.
.6 Safe and efficient means of ascertaining the amount of oil fuel
contained in any oil fuel tank shall be provided. Sounding pipes shall not
terminate in any space where the risk of ignition of spillage from the
sounding pipe might arise. In particular, they shall not terminate in
passenger or crew spaces. Other means of ascertaining the amount of oil
fuel contained in any oil fuel tank may be permitted:
6.1 in passenger ships, if such means do not require penetration
below the top of the tank, and providing their failure or over-filling of
the tanks will not permit release of fuel;
6.2 in cargo ships, providing the failure of such means or
over-filling of the tanks will not permit release of fuel. The use of
cylindrical gauge glasses is prohibited. The Administration may permit the
use of oil level gauges with flat glasses and self-closing valves between
the gauges and oil tanks.
Such other means shall be acceptable to the Administration and
shall be maintained in the proper condition to ensure their continued
accurate functioning in service.
.7 Provision shall be made to prevent overpressure in any oil tank
or in any part of the oil fuel system, including the filling pipes. Any
relief valves and air or overflow pipes shall discharge to a position
which, in the opinion of the Administration, is safe.
.8 Oil fuel pipes and their valves and fittings shall be of steel
or other approved material, except that restricted use of flexible pipes
shall be permissible in positions where the Administration is satisfied
that they are necessary. Such flexible pipes and end attachments shall be
of approved fire-resisting materials of adequate strength and shall be
constructed to the satisfaction of the Administration.
3 Lubricating oil arrangements
The arrangements for the storage, distribution and utlization of oil
used in pressure lubrication systems shall be such as to ensure the safety
of the ship and persons on board, and such arrangements in machinery
spaces of category A and whenever practicable in other machinery spaces
shall at least comply with the provisions of paragraphs 2.1, 2.4, 2.5,
2.6, 2.7 and 2.8, except that this does not preclude the use of sight
flow glasses in lubricating systems provided that they are shown by test
to have a suitable degree of fire resistance.
4 Arrangements for other flammable oils
The arrangements for the storage, distribution and utilization of
other flammable oils employed under pressure in power transmission
systems, control and activating systems and heating systems shall be such
as to ensure the safety of the ship and persons on board. In locations
where means of ignition are present, such arrangements shall at least
comply with the provisions of paragraphs 2.4 and 2.6, and with the
provisions of paragraphs 2.7 and 2. 8 in respect of strength and
construction.
5 Periodically unattended machinery spaces
In addition to the requirements of paragraphs 1 to 4, the oil fuel and
lubricating oil systems shall comply with the following:
.1 Where necessary, oil fuel and lubricating oil pipelines shall
be screened or otherwise suitably protected to avoid as far as practicable
oil spray or oil leakages on to hot surfaces or into machinery air
intakes. The number of joints in such piping systems shall be kept to a
minimum and, where practicable, leakages from high pressure oil fuel pipes
shall be collected and arrangements provided for an alarm to be given.
.2 Where daily service oil fuel tanks are filled automatically, or
by remote control, means shall be provided to prevent overflow spillages.
Other equipment which treats flammable liquids automatically, e.g. oil
fuel purifiers, which, whenever practicable, shall be installed in a
special space reserved for purifiers and their heaters, shall have
arrangements to prevent overflow spillages.
.3 Where daily service oil fuel tanks or settling tanks are fitted
with heating arrangements, a high temperature alarm shall be provided if
the flashpoint of the oil fuel can be exceeded.
Regulation 16 Ventilation systems in ships other than passengerships carrying more than 36 passengers
1 Ventilation ducts shall be of non-combustible material. Short ducts,
however, not generally exceeding 2m in length and with a cross-section
not exceeding 0.02 square m need not be non-combustible, subject to the
following conditions:
.1 these ducts shall be of a material which, in the opinion of the
Administration, has a low fire risk;
.2 they may only be used at the end of the ventilation device;
.3 they shall not be situated less than 600 mm, measured along the
duct, from an opening in an "A" or "B" class division including continuous
"B" class ceilings.
2 Where the ventilation ducts with a free-sectional area exceeding
0.02 square m pass through class "A" bulkheads or decks, the opening
shall be lined with a steel sheet sleeve unless the ducts passing through
the bulkheads or decks are of steel in the vicinity of passage through the
deck or bulkhead and the ducts and sleeves shall comply in this part with
the following:
.1 The sleeves shall have a thickness of at least 3 mm and a
length of at least 900 mm. When passing through bulkheads, this length
shall be divided preferably into 450 mm on each side of the bulkhead.
These ducts, or sleeves lining such ducts, shall be provided with fire
insulation. The insulation shall have at least the same fire integrity as
the bulkhead or deck through which the duct passes. Equivalent penetration
protection may be provided to the satisfaction of the Administration.
.2 Ducts with as free cross-sectional area exceeding 0.075 square
m shall be fitted with fire dampers in addition to the requirements of
paragraph 2.1. The fire damper shall operate automatically but shall also
be capable of being closed manually from both sides of the bulkhead or
deck. The damper shall be provided with an indicator which shows whether
the damper is open or closed. Fire dampers are not required, however,
where ducts pass through spaces surrounded by "A" class division, without
serving those spaces, provided those ducts have the same fire integrity as
the divisions which they pierce.
3 Ducts provided for the ventilation of machinery spaces of category
A, galleys, car deck spaces, ro/ro cargo spaces or special category spaces
shall not pass through accommodation spaces, service spaces or control
stations unless the ducts are either:
.1.1 constructed of steel having a thickness of at least 3 mm and
5 mm for ducts the widths or diameters of which are up to and including
300 mm and 760 mm and over respectively and, in the case of such ducts,
the widths or diameters of which are between 300 mm and 760 mm having a
thickness to be obtained by interpolation;
.1.2 suitably supported and stiffened;
.1.3 fitted with automatic fire dampers close to the boundaries
penetrated; and
.1.4 insulated to "A-60" standard from the machinery spaces,
galleys, car deck spaces, ro/ro cargo spaces or special category spaces to
a point at least 5 m beyond each fire damper;
or
.2.1 constructed of steel in accordance with paragraphs 3.1.1 and
3.1.2; and
.2.2 insulated to "A-60" standard throughout the accommodation
spaces, service spaces or control stations;
except that penetrations of main zone divisions shall also comply with
the requirements of paragraph 8.
4 Ducts provided for ventilation to accommodation spaces, service
spaces or control stations shall not pass through machinery spaces of
category A, galleys, car deck spaces, ro/ro cargo spaces or special
category spaces unless either:
.1.1 the ducts where they pass through a machinery space of
category A, galley, car deck space, ro/ro cargo space or special category
space are constructed of steel in accordance with paragraphs 3.1.1 and
3.1.2;
.1.2 automatic fire dampers are fitted close to the boundaries
penetrated; and
.1.3 the integrity of the machinery space, galley, car deck space,
ro/ro cargo space or special category space boundaries is maintained at
the penetrations;
or
.2.1 the ducts where they pass through a machinery space of
category A, galley, car deck space, ro/ro cargo space or special category
space are constructed of steel in accordance with paragraphs 3.1.1 and
3.1.2; and
.2.2 are insulated to "A-60" standard within the machinery space,
galley, car deck space, ro/ro cargo space or special category space;
except that penetrations of main zone divisions shall also comply with
the requirements of paragraph 8.
5 Ventilation ducts with a free cross-sectional area exceeding 0.02
square m passing through "B" class bulkheads shall be lined with steel
sheet sleeves of 900 mm in length divided preferably into 450 mm on each
side of the bulkheads unless the duct is of steel for this length.
6 Such measures as are practicable shall be taken in respect of
control stations outside machinery spaces in order to ensure that
ventilation, visibility and freedom from smoke are maintained, so that in
the event of fire the machinery and equipment contained therein may be
supervised and continue to function effectively. Alternative and separate
means of air supply shall be provided; air inlets of the two sources of
supply shall be so disposed that the risk of both inlets drawing in smoke
simultaneously is minimized. At the discretion of the Administration,
such requirements need not apply to control stations situated on, and
opening on to, an open deck, or where local closing arrangements would be
equally effective.
7 Where they pass through accommodation spaces or spaces containing
combustible materials, the exhaust ducts from galley ranges shall be
constructed of "A" class divisions. Each exhaust duct shall be fitted
with:
.1 a grease trap readily removable for cleaning;
.2 a fire damper located in the lower end of the duct;
.3 arrangements, operable from within the galley, for shutting off
the exhaust fans; and
.4 fixed means for extinguishing a fire within the duct.
8 Where in a passenger ship it is necessary that a ventilation duct
passes through a main vertical zone division, a fail-safe automatic
closing fire damper shall be fitted adjacent to the division. The damper
shall also be capable of being manually closed from each side of the
division. The operating position shall be readily accessible and be marked
in red light-reflecting colour. The duct between the division and the
damper shall be of steel or other equivalent material and, if necessary,
insulated to comply with the requirements of Regulation 18.1.1. The damper
shall be fitted on at least one side of the division with a visible
indicator showing whether the damper is in the open position.
9 The main inlets and outlets of all ventilation systems shall be
capable of being closed from outside the spaces being ventilated.
10 Power ventilation of accommodation spaces, service spaces, cargo
spaces, control stations and machinery spaces shall be capable of being
stopped from an easily accessible position outside the space being served.
This position should not be readily cut off in the event of a fire in the
spaces served. The means provided for stopping the power ventilation of
the machinery spaces shall be entirely separate from the means provided
for stopping ventilation of other spaces.
Regulation 17 Fireman's outfit
1 A fireman's outfit shall consist of:
1.1 Personal equipment comprising:
.1 Protective clothing of material to protect the skin from the
heat radiating from the fire and from burns and scalding by steam. The
outer surface shall be water-resistant.
.2 Boots and gloves of rubber or other electrically non-conducting
material.
.3 A rigid helmet providing effective protection against impact.
.4 An electric safety lamp (hand lantern) of an approved type with
a minimum burning period of three hours.
.5 An axe to the satisfaction of the Administration.
1.2 A breathing apparatus of an approved type which may be either:
.1 a smoke helmet or smoke mask which shall be provided with a
suitable air pump and a length of air hose sufficient to reach from the
open deck, well clear of hatch or doorway, to any part of the holds or
machinery spaces. If, in order to comply with this sub-paragraph, an air
hose exceeding 36 m in length would be necessary, a self-contained
breathing apparatus shall be substituted or provided in addition as
determined by the Administration; or
.2 a self-contained compressed air-operated breathing apparatus,
the volume of air contained in the cylinders of which shall be at least
1,200 l, or other self-contained breathing apparatus which shall be
capable of functioning for at least 30 minutes. A number of spare charges,
suitable for use with the apparatus provided, shall be available on board
to the satisfaction of the Administration.
2 For each breathing apparatus a fireproof lifeline of sufficient
length and strength shall be provided capable of being attached by means
of a snaphook to the harness of the apparatus or to a separate belt in
order to prevent the breathing apparatus becoming detached when the
lifeline is operated.
3 All ships shall carry at least two fireman's outfits complying with
the requirements of paragraph 1.
3.1 In addition, there shall be provided:
.1 in passenger ships for every 80 m, or part thereof, of the
aggregate of the lengths of all passenger spaces and service spaces on the
deck which carries such spaces or, if there is more than one such deck,
on the deck which has the largest aggregate of such lengths, two fireman's
outfits and two sets of personal equipment, each set comprising the items
stipulated in paragraphs 1.1.1, 1.1.2 and 1.1.3;
.2 in tankers, two fireman's outfits.
3.2 In passenger ships carrying more than 36 passengers for each pair
of breathing apparatus there shall be provided one water fog applicator
which shall be stored adjacent to such apparatus.
3.3 The Administration may require additional sets of personal
equipment and breathing apparatus, having due regard to the size and type
of the ship.
4 The fireman's outfits or sets of personal equipment shall be so
stored as to be easily accessible and ready for use and, where more than
one fireman's outfit or more than one set of personal equipment is
carried, they shall be stored in widely separated positions. In passenger
ships at least two fireman's outfits and one set of personal equipment
shall be available at any one position.
Regulation 18 Miscellaneous items
1.1 Where "A" class divisions are penetrated for the passage of
electric cables, pipes, trunks, ducts, etc., or for girders, beams or
other structural members, arrangements shall be made to ensure that the
fire resistance is not impaired, subject to the provisions of Regulation
30.5.
1.2 Where "B" class divisions are penetrated for the passage of
electric cables, pipes, trunks, ducts, etc., or for the fitting of
ventilation terminals, lighting fixtures and similar devices, arrangements
shall be made to ensure that the fire resistance is not impaired.
2.1 Pipes penetrating "A" or "B" class divisions shall be of materials
approved by the Administration having regard to the temperature such
divisions are required to withstand.
2.2 Where the Administration may permit the conveying of oil and
combustible liquids through accommodation and service spaces, the pipes
conveying oil or combustible liquids shall be of a material approved by
the Administration having regard to the fire risk.
2.3 Materials readily rendered ineffective by heat shall not be used
for overboard scuppers, sanitary discharges, and other outlets which are
close to the water-line and where the failure of the material in the event
of fire would give rise to danger of flooding.
3 Electric radiators, if used, shall be fixed in position and so
constructed as to reduce fire risks to a minimum. No such radiators shall
be fitted with an element so exposed that clothing, curtains, or other
similar materials can be scorched or set on fire by heat from the element.
4 Cellulose-nitrate based films shall not be used for cinematograph
installations.
5 All waste-receptacles shall be constructed of non-combustible
materials with no openings in the sides or bottom.
6 In spaces where penetration of oil products is possible, the surface
of insulation shall be impervious to oil or oil vapours.
Regulation 19 International shore connexion *
[* Reference is made to the recommendation contained in resolution
A.470 (XII) adopted by the Organization entitled "International Shore
Connexion (shore side)".]
1 Ships of 500 tons gross tonnage and upwards shall be provided with
at least one international shore connexion, complying with provisions of
paragraph 3.
2 Facilities shall be available enabling such a connexion to be used
on either side of the ship.
3 Standard dimensions of flanges for the international shore connexion
shall be in accordance with the following table:
|-------------------
| Description | Dimension |
|--------|----------|
| Outside diameter | 178 mm |
|--------|----------|
| Inside diameter | 64 mm |
|--------|----------|
| Bolt circle diameter | 132 mm |
|--------|----------|
| Slots in flange | 4 holes 19 mm in diameter spaced |
| equidistantly on a bolt circle |
| of the above diameter, slotted |
| to the flange periphery |
|--------|----------|
| Flange thickness | 14.5 mm minimum |
|--------|----------|
| Bolts and nuts | 4, each of 16 mm diameter, |
| 50 mm in length |
|-------------------
4 The connexion shall be of steel or other suitable material and shall
be designed for 1.0
2 N/mm services. The flange shall have a flat face on one side and on
the other shall be permanently attached to a coupling that will fit the
ship's hydrant and hose. The connexion
2 shall be kept aboard the ship together with a gasket of any material
suitable for 1.0 N/mm services, together with four 16 mm bolts, 50 mm in
length and eight washers.
Regulation 20 Fire control plans
1 In all ships general arrangement plans shall be permanently
exhibited for the guidance of the ship's officers, showing clearly for
each deck the control stations, the various fire sections enclosed by "A"
class divisions, the sections enclosed by "B" class divisions together
with particulars of the fire detection and fire alarm systems, the
sprinkler installation, the fire-extinguishing appliances, means of access
to different compartments, decks, etc. and the ventilating system
including particulars of the fan control positions, the position of
dampers and identification numbers of the ventilating fans serving each
section. Alternatively, at the discretion of the Administration, the
aforementioned details may be set out in a booklet, a copy of which shall
be supplied to each officer, and one copy shall at all times be available
on board in an accessible position. Plans and booklets shall be kept up to
date, any alterations being recorded thereon as soon as practicable.
Description in such plans and booklets shall be in the national language.
If the language is neither English nor French, a translation into one of
those languages shall be included. In addition, instructions concerning
the maintenance and operation of all the equipment and installations on
board for the fighting and containment of fire shall be kept under one
cover, readily available in an accessible position.
2 In all ships a duplicate set of fire control plans or a booklet
containing such plans shall be permanently stored in a prominently marked
weathertight enclosure outside the deckhouse for the assistance of
shoreside fire-fighting personnel.
Regulation 21 Ready availability of fire-extinguishing appliances
In all ships, fire-extinguishing appliances shall be kept in good
order and available for immediate use at all times during the voyage.
Regulation 22 Acceptance of substitutes
1 This Regulation applies to all ships.
2 Where in this Chapter any special type of appliance, apparatus,
extinguishing medium or arrangement is specified in any ship, any other
type of appliance etc., may be allowed, provided the Administration is
satisfied that it is not less effective.
PART D FIRE SAFETY MEASURES FOR PASSENGER SHIPS
Regulation 23 Structure
1 The hull, superstructure, structural bulkheads, decks and deckhouses
shall be constructed of steel or other equivalent material. For the
purpose of applying the definition of steel or other equivalent material
as given in Regulation 3.7 the "applicable fore exposure" shall be
according to the integrity and insulation standards given in the tables of
Regulation 26 and 27. For example where divisions such as decks or sides
and ends of deckhouses are permitted to have "B-0" fire integrity, the
"applicable fire exposure" shall be half an hour.
2 However, in cases where any part of the structure is of aluminium
alloy, the following shall apply:
.1 The insulation of aluminium alloy components of "A" or "B"
class divisions, except structure which, in the opinion of the
Administration, is non-load-bearing, shall be such that the temperature of
the structural core does not rise more than 200 ¡æabove the ambient
temperature at any time during the applicable fire exposure to the
standard fire test.
.2 Special attention shall be given to the insulation of aluminium
alloy components of columns, stanchions and other structural members
required to support lifeboat and liferaft stowage, launching and
embarkation areas, and "A" and "B" class divisions to ensure:
.2.1 that for such members supporting lifeboat and liferaft areas
and "A" class divisions, the temperature rise limitation specified in
paragraph 2.1 shall apply at the end of one hour; and
.2.2 that for such members required to support "B" class
divisions, the temperature rise limitation specified in paragraph 2.1
shall apply at the end of half an hour.
3 Crowns and casings of machinery spaces of category A shall be of
steel construction adequately insulated and openings therein, if any,
shall be suitably arranged and protected to prevent the spread of fire.
Regulation 24 Main vertical zones and horizontal zones
1.1 For ships carrying more than 36 passengers, the hull,
superstructure and deckhouses shall be subdivided into main vertical zones
by "A" class divisions. Steps and recesses shall be kept to a minimum, but
where they are necessary they shall also be "A" class divisions. These
divisions shall have insulation values in accordance with tables in
Regulation 26.
1.2 For ships carrying not more than 36 passengers, the hull,
superstructure and deckhouses in way of accommodation and service spaces
shall be subdivided into main vertical zones by "A" class division. These
divisions shall have insulation values in accordance with tables in
Regulation 27.
2 As far as practicable, the bulkheads forming the boundaries of the
main vertical zones above the bulkhead deck shall be in line with
watertight subdivision bulkheads situated immediately below the bulkhead
deck.
3 Such bulkheads shall extend from deck to deck and to the shell or
other boundaries.
4 Where a main vertical zone is subdivided by horizontal "A" class
divisions into horizontal zones for the purpose of providing an
appropriate barrier between sprinklered and non-sprinklered zones of the
ship, the divisions shall extend between adjacent main vertical zone
bulkheads and to the shell or exterior boundaries of the ship and shall be
insulated in accordance with the fire insulation and integrity values
given in table 26.3 or in table 27.2.
5.1 On ships designed for special purposes, such as automobile or
railroad car ferries, where the provision of main vertical zone bulkheads
would defeat the purpose for which the ship is intended, equivalent means
for controlling and limiting a fire shall be substituted and specifically
approved by the Administration.
5.2 However, in a ship with special category spaces, any such space
shall comply with the applicable provisions of Regulation 37 and in so far
as such compliance would be inconsistent with compliance with other
requirements of this Part, the requirements of Regulation 37 shall
prevail.
Regulation 25 Bulkheads within a main vertical zone
1.1 For ships carrying more than 36 passengers all bulkheads which are
not required to be "A" class divisions shall be at least "B" class or "C"
class divisions as prescribed in the tables in Regulation 26.
1.2 For ships carrying not more than 36 passengers all bulkheads
within accommodation and service spaces which are not required to be "A"
class divisions shall be at least "B" class or "C" class divisions as
prescribed in the tables in Regulation 27.
1.3 All such divisions may be faced with combustible materials in
accordance with the provisions of Regulation 34.
2 All corridor bulkheads where not required to be "A" class shall be
"B" class divisions which shall extend from deck to deck except:
.1 when continuous "B" class ceilings or linings are fitted on
both sides of the bulkhead, the portion of the bulkhead behind the
continuous ceiling or lining shall be of material which, in thickness and
composition, is acceptable in the construction of "B" class divisions but
which shall be required to meet "B" class integrity standards only in so
far as is reasonable and practicable in the opinion of the Administration;
.2 in the case of a ship protected by an automatic sprinkler
system complying with the provisions of Regulation 12 the corridor
bulkheads of "B" class materials may terminate at a ceiling in the
corridor provided such a ceiling is of material which, in thickness and
composition, is acceptable in the construction of "B" class divisions.
Notwithstanding the requirements of Regulations 26 and 27 such bulkheads
and ceilings shall be required to meet "B" class integrity standards only
in so far as is reasonable and practicable in the opinion of the
Administration. All doors and frames in such bulkheads shall be of
non-combustible materials and shall be so constructed and erected as to
provide substantial fire resistance to the satisfaction of the
Administration.
3 All bulkheads required to be "B" class divisions, except corridor
bulkheads, shall extend from deck to deck and to the shell or other
boundaries unless continuous "B" class ceilings or linings are fitted on
both sides of the bulkhead, in which case the bulkhead may terminate at
the continuous ceiling or lining.
Regulation 26 Fire integrity of bulkheads and decks in ships car-rying more than 36 passengers
1 In addition to complying with the specific provisions for fire
integrity of bulkheads and decks mentioned elsewhere in this Part, the
minimum fire integrity of all bulkheads and decks shall be as prescribed
in tables 26.1 to 26.4. Where, due to any particular structural
arrangements in the ship, difficulty is experienced in determining from
the tables the minimum fire integrity value of any divisions, such values
shall be determined to the satisfaction of the Administration.
2 The following requirements shall govern application of the tables:
.1 Table 26.1 shall apply to bulkheads bounding main vertical
zones or horizontal zones.
Table 26.2 shall apply to bulkheads not bounding either main
vertical zones or horizontal zones.
Table 26.3 shall apply to decks forming steps in main vertical
zones or bounding horizontal zones.
Table 26.4 shall apply to decks not forming steps in main
vertical zones nor bounding horizontal zones.
.2 for the purpose of determining the appropriate fire integrity
standards to be applied to boundaries between adjacent spaces, such spaces
are classified according to their fire risk as shown in categories (1) to
(14) below. Where the contents and use of a space are such that there is a
doubt as to its classification for the purpose of this Regulation, it
shall be treated as a space within the relevant category having the most
stringent boundary requirements. The title of each category is intended to
be typical rather than restrictive. The number in parentheses preceding
each category refers to the applicable column or row number in the tables.
(1) Control stations
Spaces containing emergency sources of power and lighting.
Wheelhouse and chartroom.
Spaces containing the ship's radio equipment.
Fire-extinguishing rooms, fire control and recording
stations.
Control room for propulsion machinery when located outside
the propulsion machinery space.
Spaces containing centralized fire alarm equipment.
Spaces containing centralized emergency public address
system stations and equipment.
(2) Stairways
Interior stairways, lifts and escalators (other than those
wholly contained within the machinery spaces) for passengers and crew and
enclosures thereto.
In this connexion a stairway which is enclosed at only one
level shall be regarded as part of the space from which it is not
separated by a fire door.
(3) Corridors
Passenger and crew corridors and lobbies.
(4) Lifeboat and liferaft handling and embarkation stations
Open deck spaces and enclosed promenades forming lifeboat
and liferaft embarkation and lowering stations.
(5) Open deck spaces
Open deck spaces and enclosed promenades clear of lifeboat
and liferaft embarkation and lowering stations.
Air space (the space outside superstructures and
deckhouses).
(6) Accommodation spaces of minor fire risk
Cabins containing furniture and furnishings of restricted
fire risk.
Offices and dispensaries containing furniture and
furnishings of restricted fire risk.
Public spaces containing furniture and furnishings of
restricted fire risk and having a deck area of less than 50 square m .
(7) Accommodation spaces of moderate fire risk
Spaces as in category (6) above but containing furniture
and furnishings of other than restricted fire risk.
Public spaces containing furniture and furnishings of
restricted fire risk and having a deck area of 50 square m or more.
Isolated lockers and small store-rooms in accommodation
spaces.
Sale shops.
| 1 | 2 | 3 | 4 | 5 |
|