Home | Hotels | Hotels Video | China Flights | China Train Tickets | Main cities | China map | Contact us | Reservation Status  

 China Law information

| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFEAT SEA, 1974

AMENDMENTS TO THE INTERNATIONAL CONVENTION FOR THE SAFETY OF LIFEAT SEA, 1974 [Adopted on 20 November 1981 by Resolution MSC .1 (XLV)] 5.1 An independent power pump shall be provided solely for the purpose of continuing automatically the discharge of water from the sprinklers.

The pump shall be brought into action automatically by the pressure drop in the system before the standing fresh water charge in the pressure tank is completely exhausted.

5.2 The pump and the piping system shall be capable of maintaining the necessary pressure at the level of the highest sprinkler to ensure a continuous output of water sufficient for the 2 simultaneous coverage of a minimum area of 280 m at the application rate specified in paragraph 3.

5.3 The pump shall have fitted on the delivery side a test valve with a short open-ended discharge pipe. The effective area through the valve and pipe shall be adequate to permit the release of the required pump output while maintaining the pressure in the system specified in paragraph 4.1.

5.4 The sea inlet to the pump shall wherever possible be in the space containing the pump and shall be so arranged that when the ship is afloat it will not be necessary to shut off the supply of sea-water to the pump for any purpose other than the inspection or repair of the pump.

6 The sprinkler pump and tank shall be situated in a position reasonably remote from any machinery space of category A and shall not be situated in any space required to be protected by the sprinkler system.

7.1 In passenger ships there shall be not less than two sources of power supply for the seawater pump and automatic alarm and detection system. Where the sources of power for the pump are electrical, these shall be a main generator and an emergency source of power. One supply for the pump shall be taken from the main switchboard, and one from the emergency switchboard by separate feeders reserved solely for that purpose. The feeders shall be so arranged as to avoid galleys, machinery spaces and other enclosed space of high risk except in so far as it is necessary to reach the appropriate switchboards, and shall be run to an automatic change-over switch situated near the sprinkler pump. This switch shall permit the supply of power from the main switchboard so long as a supply is available therefrom, and be so designed that upon failure of that supply it will automatically change over to the supply from the emergency switchboard. The switches on the main switchboard and the emergency switchboard shall be clearly labelled and normally kept closed.

No other switch shall be permitted in the feeders concerned. One of the sources of power supply for the alarm and detection system shall be an emergency source. Where one of the sources of power for the pump is an internal combustion engine it shall, in addition to complying with the provisions of paragraph 6, be so situated that a fire in any protected space will not affect the air supply to the machinery.

7.2 In cargo ships there shall not be less than two sources of power supply for the sea-water pump and automatic alarm and detection system. If the pump is electrically driven it shall be connected to the main source of electrical power, which shall be capable of being supplied by at least two generators. The feeders shall be so arranged as to avoid galleys, machinery spaces and other enclosed spaces of high fire risk except in so far as it is necessary to reach the appropriate switchboards. One of the sources of power supply for the alarm and detection system shall be an emergency source. Where one of the sources of power for the pump is an internal combustion engine it shall, in addition to complying with the provisions of paragraph 6, be so situated that a fire in any protected space will not affect the air supply to the machinery.

8 The sprinkler system shall have a connexion from the ship's fire main by way of a lockable screw-down non-return valve at the connexion which will prevent a backflow from the sprinkler system to the fire main.

9.1 A test valve shall be provided for testing the automatic alarm for each section of sprinklers by a discharge of water equivalent to the operation of one sprinkler. The test valve for each section shall be situated near the stop valve for that section.

9.2 Means shall be provided for testing the automatic operation of the pump on reduction of pressure in the system.

9.3 Switches shall be provided at one of the indicating positions referred to in paragraph 1. 2 which will enable the alarm and the indicators for each section of sprinklers to be tested.

10 Spare sprinkler heads shall be provided for each section of sprinklers to the satisfaction of the Administration.

Regulation 13 Fixed fire detection and fire alarm systems 1 General requirements 1.1 Any required fixed fire detection and fire alarm system with manually operated call points shall be capable of immediate operation at all times.

1.2 Power supplies and electric circuits necessary for the operation of the system shall be monitored for loss of power of fault conditions as appropriate. Occurrence of a fault condition shall initiate a visual and audible fault signal at the control panel which shall be distinct from a fire signal.

1.3 There shall be not less than two sources of power supply for the electrical equipment used in the operation of the fire detection and fire alarm system, one of which shall be an emergency source. The supply shall be provided by separate feeders reserved solely for that purpose. Such feeders shall run to an automatic change-over switch situated in or adjacent to the control panel for the fire detection system.

1.4 Detectors and manually operated call points shall be grouped into sections. The activation of any detector or manually operated call point shall initiate a visual and audible fire signal at the control panel and indicating units. If the signals have not received attention within two minutes an audible alarm shall be automatically sounded throughout the crew accommodation and service spaces, control stations and machinery spaces of category A. This alarm sounder system need not be an integral part of the detection system.

1.5 The control panel shall be located on the navigating bridge or in the main fire control station.

1.6 Indicating units shall denote the section in which a detector or manually operated call point has operated. At least one unit shall be so located that it is easily accessible to responsible members of the crew at all times, when at sea or in port except when the ship is out of service.

One indicating unit shall be located on the navigating bridge if the control panel is located in the main fire control station.

7 Clear information shall be displayed on or adjacent to each indicating unit about the spaces covered and the location of the sections.

1.8 No section covering more than one deck within accommodation, service and control stations shall normally be permitted except a section which covers an enclosed stairway. In order to avoid delay in identifying the source of fire, the number of enclosed spaces included in each section shall be limited as determined by the Administration. In no case shall more than fifty enclosed spaces be permitted in any section.

1.9 In passenger ships a section of detectors shall not serve spaces on both sides of the ship nor on more than one deck and neither shall it be situated in more than one main vertical zone except that the Administration, if it is satisfied that the protection of the ship against fire will not thereby be reduced, may permit such a section of detectors to serve both sides of the ship and more than one deck.

1.10 A section of fire detectors which covers a control station, a service space or an accommodation space shall not include a machinery space of category A.

1.11 Detectors shall be operated by heat, smoke or other products of combustion, flame, or any combination of these factors. Detectors operated by other factors indicative of incipient fires may be considered by the Administration provided that they are no less sensitive than such detectors. Flame detectors shall only be used in addition to smoke or heat detectors.

1.12 Suitable instructions and components spares for testing and maintenance shall be provided.

1.13 The function of the detection system shall be periodically tested to the satisfaction of the Administration by means of equipment producing hot air at the appropriate temperature, or smoke or aerosol particles having the appropriate range of density or particle size, or other phenomena associated with incipient fires to which the detector is designed to respond. All detectors shall be of a type such that they can be tested for correct operation and restored to normal surveillance without the renewal of any component.

1.14 The fire detection system shall not be used for any other purpose, except that closing of fire doors and similar functions may be permitted at the control panel.

2 Installation requirements 2.1 Manual call points shall be installed throughout the accommodation spaces, service spaces and control stations. One manual call point shall be located at each exit. Manual call points shall be readily accessible in the corridors of each deck such that no part of the corridor is more than 20 m from a manual call point.

2.2 Smoke detectors shall be installed in all stairways, corridors and escape routes within accommodation spaces. Consideration shall be given to the installation of special purpose smoke detectors within ventilation ducting.

2.3 Where a fixed fire detection and fire alarm system is required for the protection of spaces other than those specified in paragraph 2.2, at least one detector complying with paragraph 1.11 shall be installed in each such space.

2.4 Detectors shall be located for optimum performance. Positions near beams and ventilation ducts or other positions where patterns of air flow could adversely affect performance and positions where impact or physical damage is likely shall be avoided. In general, detectors which are located on the overhead shall be a minimum distance of 0.5 m away from bulkheads.

2.5 The maximum spacing of detectors shall be in accordance with the table below: |----------------------- | Type of | Maximum floor area | Maximum distance apart | Maximum distance away | | detector | per detector | between centres | from bulkheads | |----|------|--------|-------| | 2 | | | Heat | 37 m | 9 m | 4.5 m | |----|------|--------|-------| | 2 | | | Smoke | 74 m | 11 m | 5.5 m | |----------------------- The Administration may require or permit other spacings based upon test data which demonstrate the characteristics of the detectors.

2.6 Electrical wiring which forms part of the system shall be so arranged as to avoid galleys, machinery spaces of category A, and other enclosed spaces of high fire risk except where it is necessary to provide for fire detection or fire alarm in such spaces or to connect to the appropriate power supply.

3 Design requirements 3.1 The system and equipment shall be suitably designed to withstand supply voltage variation and transients, ambient temperature changes, vibration, humidity, shock, impact and corrosion normally encountered in ships.

3.2 Smoke detectors required by paragraph 2.2 shall be certified to operate before the smoke density exceeds 12.5 per cent obscuration per metre, but not until the smoke density exceeds 2 per cent obscuration per metre. Smoke detectors to be installed in other spaces shall operate within sensitivity limits to the satisfaction of the Administration having regard to the avoidance of detector insensitivity or oversensitivity.

3.3 Heat detectors shall be certified to operate before the temperature exceeds 78¡æ but not until the temperature exceeds 54 ¡æ, when the temperature is raised to those limits at a rate less than 1¡æ per minute. At higher rates of temperature rise, the heat detector shall operate within temperature limits to the satisfaction of the Administration having regard to the avoidance of detector insensitivity or oversensitivity.

3.4 At the discretion of the Administration, the permissible temperature of operation of heat detectors may be increased to 30¡æ above the maximum deckhead temperature in drying rooms and similar spaces of a normal high ambient temperature.

Regulation 14 Fixed fire detection and fire alarm systems for pe-riodically unattended machinery spaces 1 A fixed fire detection and fire alarm system in accordance with the relevant provisions of Regulation 13 shall be installed in periodically unattended machinery spaces.

2 This fire detection system shall be so designed and the detectors so positioned as to detect rapidly the onset of fire in any part of those spaces an d under any normal conditions of operation of the machinery and variations of ventilation as required by the possible range of ambient temperature. Except in spaces of restricted height and where their use is specially appropriate, detection systems using only thermal detector shall not be permitted. The detection system shall initiate audible and visual alarms distinct in both respects from the alarms of any other system not indicating fire, in sufficient places to ensure that the alarms are heard and observed on the navigating bridge and by a responsible engineer officer. When the navigating bridge is unmanned the alarm shall sound in a place where a responsible member of the crew is on duty.

3 After installation the system shall be tested under varying conditions of engine operation and ventilation.

Regulation 15 Arrangements for oil fuel, lubricating oil and otherflammable oils 1 Limitations in the use of oil as fuel The following limitations shall apply to the use of oil as fuel: .1 Except as otherwise permitted by this paragraph, no oil fuel with a flashpoint of less than 60 ¡æ shall be used.

.2 In emergency generators oil fuel with a flashpoint of not less than 43 ¡æ may be used.

.3 Subject to such additional precautions as it may consider necessary and on condition that the ambient temperature of the space in which such oil fuel is stored or used shall not be allowed to rise to within 10¡æ below the flashpoint of the oil fuel, the Administration may permit the general use of oil fuel having a flashpoint of less than 60¡æ but not less than 43¡æ.

.4 In cargo ships the use of fuel having a lower flashpoint than otherwise specified in this paragraph, for example crude oil, may be permitted provided that such fuel is not stored in any machinery space and subject to the approval by the Administration of the complete installation.

The flashpoint of oils shall be determined by an approved closed cup method.

2 Oil fuel arrangements In a ship in which oil fuel is used, the arrangements for the storage, distribution and utilization of the oil fuel shall be such as to ensure the safety of the ship and persons on board and shall at least comply with the following provisions: .1 As far as practicable, parts of the oil fuel system containing heated oil under pressureexceeding 0.18 N/square mm shall not be placed in a concealed position such that defects and leakage cannot readily be observed .The machinery spaces in way of such parts of the oil fuel system shall be adequately illuminated.

.2 The ventilation of machinery spaces shall be sufficient under all normal conditions to prevent accumulation of oil vapour.

.3 As far as practicable, oil fuel tanks shall be part of the ship's structure and shall be located outside machinery spaces of category A. Where oil fuel tanks, other than double bottom tanks, are necessarily located adjacent to or within machinery spaces of category A, at least one of their vertical sides shall be contiguous to the machinery space boundaries, and shall preferably have a common boundary with the double bottom tanks, and the area of the tank boundary common with the machinery spaces shall be kept to a minimum. Where such tanks are situated within the boundaries of machinery spaces of category A they shall not contain oil fuel having a flashpoint of less than 60¡æ. In general the use of free standing oil fuel tanks shall be avoided. When such tanks are employed their use shall be prohibited in category A machinery spaces on passenger ships. Where permitted, they shall be placed in an oil-tight spill tray of ample size having a suitable drain pipe leading to a suitably sized spill oil tank.

.4 No oil fuel tank shall be situated where spillage or leakage therefrom can constitute a hazard by falling on heated surfaces.

Precautions shall be taken to prevent any oil that may escape under pressure from any pump, filter or heater from coming into contact with heated surfaces.

.5 Every oil fuel pipe, which, if damaged, would allow oil to escape from a storage, settling or daily service tank situated above the double bottom shall be fitted with a cock or valve directly on the tank capable of being closed from a safe position outside the space concerned in the event of a fire occurring in the space in which such tanks are situated. In the special case of deep tanks situated in any shaft or pipe tunnel or similar space, valves on the tank shall be fitted but control in the event of fire may be effected by means of an additional valve on the pipe or pipes outside the tunnel or similar space. If such additional valve is fitted in the machinery space it shall be operated from a position outside this space.

.6 Safe and efficient means of ascertaining the amount of oil fuel contained in any oil fuel tank shall be provided. Sounding pipes shall not terminate in any space where the risk of ignition of spillage from the sounding pipe might arise. In particular, they shall not terminate in passenger or crew spaces. Other means of ascertaining the amount of oil fuel contained in any oil fuel tank may be permitted: 6.1 in passenger ships, if such means do not require penetration below the top of the tank, and providing their failure or over-filling of the tanks will not permit release of fuel; 6.2 in cargo ships, providing the failure of such means or over-filling of the tanks will not permit release of fuel. The use of cylindrical gauge glasses is prohibited. The Administration may permit the use of oil level gauges with flat glasses and self-closing valves between the gauges and oil tanks.

Such other means shall be acceptable to the Administration and shall be maintained in the proper condition to ensure their continued accurate functioning in service.

.7 Provision shall be made to prevent overpressure in any oil tank or in any part of the oil fuel system, including the filling pipes. Any relief valves and air or overflow pipes shall discharge to a position which, in the opinion of the Administration, is safe.

.8 Oil fuel pipes and their valves and fittings shall be of steel or other approved material, except that restricted use of flexible pipes shall be permissible in positions where the Administration is satisfied that they are necessary. Such flexible pipes and end attachments shall be of approved fire-resisting materials of adequate strength and shall be constructed to the satisfaction of the Administration.

3 Lubricating oil arrangements The arrangements for the storage, distribution and utlization of oil used in pressure lubrication systems shall be such as to ensure the safety of the ship and persons on board, and such arrangements in machinery spaces of category A and whenever practicable in other machinery spaces shall at least comply with the provisions of paragraphs 2.1, 2.4, 2.5, 2.6, 2.7 and 2.8, except that this does not preclude the use of sight flow glasses in lubricating systems provided that they are shown by test to have a suitable degree of fire resistance.

4 Arrangements for other flammable oils The arrangements for the storage, distribution and utilization of other flammable oils employed under pressure in power transmission systems, control and activating systems and heating systems shall be such as to ensure the safety of the ship and persons on board. In locations where means of ignition are present, such arrangements shall at least comply with the provisions of paragraphs 2.4 and 2.6, and with the provisions of paragraphs 2.7 and 2. 8 in respect of strength and construction.

5 Periodically unattended machinery spaces In addition to the requirements of paragraphs 1 to 4, the oil fuel and lubricating oil systems shall comply with the following: .1 Where necessary, oil fuel and lubricating oil pipelines shall be screened or otherwise suitably protected to avoid as far as practicable oil spray or oil leakages on to hot surfaces or into machinery air intakes. The number of joints in such piping systems shall be kept to a minimum and, where practicable, leakages from high pressure oil fuel pipes shall be collected and arrangements provided for an alarm to be given.

.2 Where daily service oil fuel tanks are filled automatically, or by remote control, means shall be provided to prevent overflow spillages.

Other equipment which treats flammable liquids automatically, e.g. oil fuel purifiers, which, whenever practicable, shall be installed in a special space reserved for purifiers and their heaters, shall have arrangements to prevent overflow spillages.

.3 Where daily service oil fuel tanks or settling tanks are fitted with heating arrangements, a high temperature alarm shall be provided if the flashpoint of the oil fuel can be exceeded.

Regulation 16 Ventilation systems in ships other than passengerships carrying more than 36 passengers 1 Ventilation ducts shall be of non-combustible material. Short ducts, however, not generally exceeding 2m in length and with a cross-section not exceeding 0.02 square m need not be non-combustible, subject to the following conditions: .1 these ducts shall be of a material which, in the opinion of the Administration, has a low fire risk; .2 they may only be used at the end of the ventilation device; .3 they shall not be situated less than 600 mm, measured along the duct, from an opening in an "A" or "B" class division including continuous "B" class ceilings.

2 Where the ventilation ducts with a free-sectional area exceeding 0.02 square m pass through class "A" bulkheads or decks, the opening shall be lined with a steel sheet sleeve unless the ducts passing through the bulkheads or decks are of steel in the vicinity of passage through the deck or bulkhead and the ducts and sleeves shall comply in this part with the following: .1 The sleeves shall have a thickness of at least 3 mm and a length of at least 900 mm. When passing through bulkheads, this length shall be divided preferably into 450 mm on each side of the bulkhead.

These ducts, or sleeves lining such ducts, shall be provided with fire insulation. The insulation shall have at least the same fire integrity as the bulkhead or deck through which the duct passes. Equivalent penetration protection may be provided to the satisfaction of the Administration.

.2 Ducts with as free cross-sectional area exceeding 0.075 square m shall be fitted with fire dampers in addition to the requirements of paragraph 2.1. The fire damper shall operate automatically but shall also be capable of being closed manually from both sides of the bulkhead or deck. The damper shall be provided with an indicator which shows whether the damper is open or closed. Fire dampers are not required, however, where ducts pass through spaces surrounded by "A" class division, without serving those spaces, provided those ducts have the same fire integrity as the divisions which they pierce.

3 Ducts provided for the ventilation of machinery spaces of category A, galleys, car deck spaces, ro/ro cargo spaces or special category spaces shall not pass through accommodation spaces, service spaces or control stations unless the ducts are either: .1.1 constructed of steel having a thickness of at least 3 mm and 5 mm for ducts the widths or diameters of which are up to and including 300 mm and 760 mm and over respectively and, in the case of such ducts, the widths or diameters of which are between 300 mm and 760 mm having a thickness to be obtained by interpolation; .1.2 suitably supported and stiffened; .1.3 fitted with automatic fire dampers close to the boundaries penetrated; and .1.4 insulated to "A-60" standard from the machinery spaces, galleys, car deck spaces, ro/ro cargo spaces or special category spaces to a point at least 5 m beyond each fire damper; or .2.1 constructed of steel in accordance with paragraphs 3.1.1 and 3.1.2; and .2.2 insulated to "A-60" standard throughout the accommodation spaces, service spaces or control stations; except that penetrations of main zone divisions shall also comply with the requirements of paragraph 8.

4 Ducts provided for ventilation to accommodation spaces, service spaces or control stations shall not pass through machinery spaces of category A, galleys, car deck spaces, ro/ro cargo spaces or special category spaces unless either: .1.1 the ducts where they pass through a machinery space of category A, galley, car deck space, ro/ro cargo space or special category space are constructed of steel in accordance with paragraphs 3.1.1 and 3.1.2; .1.2 automatic fire dampers are fitted close to the boundaries penetrated; and .1.3 the integrity of the machinery space, galley, car deck space, ro/ro cargo space or special category space boundaries is maintained at the penetrations; or .2.1 the ducts where they pass through a machinery space of category A, galley, car deck space, ro/ro cargo space or special category space are constructed of steel in accordance with paragraphs 3.1.1 and 3.1.2; and .2.2 are insulated to "A-60" standard within the machinery space, galley, car deck space, ro/ro cargo space or special category space; except that penetrations of main zone divisions shall also comply with the requirements of paragraph 8.

5 Ventilation ducts with a free cross-sectional area exceeding 0.02 square m passing through "B" class bulkheads shall be lined with steel sheet sleeves of 900 mm in length divided preferably into 450 mm on each side of the bulkheads unless the duct is of steel for this length.

6 Such measures as are practicable shall be taken in respect of control stations outside machinery spaces in order to ensure that ventilation, visibility and freedom from smoke are maintained, so that in the event of fire the machinery and equipment contained therein may be supervised and continue to function effectively. Alternative and separate means of air supply shall be provided; air inlets of the two sources of supply shall be so disposed that the risk of both inlets drawing in smoke simultaneously is minimized. At the discretion of the Administration, such requirements need not apply to control stations situated on, and opening on to, an open deck, or where local closing arrangements would be equally effective.

7 Where they pass through accommodation spaces or spaces containing combustible materials, the exhaust ducts from galley ranges shall be constructed of "A" class divisions. Each exhaust duct shall be fitted with: .1 a grease trap readily removable for cleaning; .2 a fire damper located in the lower end of the duct; .3 arrangements, operable from within the galley, for shutting off the exhaust fans; and .4 fixed means for extinguishing a fire within the duct.

8 Where in a passenger ship it is necessary that a ventilation duct passes through a main vertical zone division, a fail-safe automatic closing fire damper shall be fitted adjacent to the division. The damper shall also be capable of being manually closed from each side of the division. The operating position shall be readily accessible and be marked in red light-reflecting colour. The duct between the division and the damper shall be of steel or other equivalent material and, if necessary, insulated to comply with the requirements of Regulation 18.1.1. The damper shall be fitted on at least one side of the division with a visible indicator showing whether the damper is in the open position.

9 The main inlets and outlets of all ventilation systems shall be capable of being closed from outside the spaces being ventilated.

10 Power ventilation of accommodation spaces, service spaces, cargo spaces, control stations and machinery spaces shall be capable of being stopped from an easily accessible position outside the space being served.

This position should not be readily cut off in the event of a fire in the spaces served. The means provided for stopping the power ventilation of the machinery spaces shall be entirely separate from the means provided for stopping ventilation of other spaces.

Regulation 17 Fireman's outfit 1 A fireman's outfit shall consist of: 1.1 Personal equipment comprising: .1 Protective clothing of material to protect the skin from the heat radiating from the fire and from burns and scalding by steam. The outer surface shall be water-resistant.

.2 Boots and gloves of rubber or other electrically non-conducting material.

.3 A rigid helmet providing effective protection against impact.

.4 An electric safety lamp (hand lantern) of an approved type with a minimum burning period of three hours.

.5 An axe to the satisfaction of the Administration.

1.2 A breathing apparatus of an approved type which may be either: .1 a smoke helmet or smoke mask which shall be provided with a suitable air pump and a length of air hose sufficient to reach from the open deck, well clear of hatch or doorway, to any part of the holds or machinery spaces. If, in order to comply with this sub-paragraph, an air hose exceeding 36 m in length would be necessary, a self-contained breathing apparatus shall be substituted or provided in addition as determined by the Administration; or .2 a self-contained compressed air-operated breathing apparatus, the volume of air contained in the cylinders of which shall be at least 1,200 l, or other self-contained breathing apparatus which shall be capable of functioning for at least 30 minutes. A number of spare charges, suitable for use with the apparatus provided, shall be available on board to the satisfaction of the Administration.

2 For each breathing apparatus a fireproof lifeline of sufficient length and strength shall be provided capable of being attached by means of a snaphook to the harness of the apparatus or to a separate belt in order to prevent the breathing apparatus becoming detached when the lifeline is operated.

3 All ships shall carry at least two fireman's outfits complying with the requirements of paragraph 1.

3.1 In addition, there shall be provided: .1 in passenger ships for every 80 m, or part thereof, of the aggregate of the lengths of all passenger spaces and service spaces on the deck which carries such spaces or, if there is more than one such deck, on the deck which has the largest aggregate of such lengths, two fireman's outfits and two sets of personal equipment, each set comprising the items stipulated in paragraphs 1.1.1, 1.1.2 and 1.1.3; .2 in tankers, two fireman's outfits.

3.2 In passenger ships carrying more than 36 passengers for each pair of breathing apparatus there shall be provided one water fog applicator which shall be stored adjacent to such apparatus.

3.3 The Administration may require additional sets of personal equipment and breathing apparatus, having due regard to the size and type of the ship.

4 The fireman's outfits or sets of personal equipment shall be so stored as to be easily accessible and ready for use and, where more than one fireman's outfit or more than one set of personal equipment is carried, they shall be stored in widely separated positions. In passenger ships at least two fireman's outfits and one set of personal equipment shall be available at any one position.

Regulation 18 Miscellaneous items 1.1 Where "A" class divisions are penetrated for the passage of electric cables, pipes, trunks, ducts, etc., or for girders, beams or other structural members, arrangements shall be made to ensure that the fire resistance is not impaired, subject to the provisions of Regulation 30.5.

1.2 Where "B" class divisions are penetrated for the passage of electric cables, pipes, trunks, ducts, etc., or for the fitting of ventilation terminals, lighting fixtures and similar devices, arrangements shall be made to ensure that the fire resistance is not impaired.

2.1 Pipes penetrating "A" or "B" class divisions shall be of materials approved by the Administration having regard to the temperature such divisions are required to withstand.

2.2 Where the Administration may permit the conveying of oil and combustible liquids through accommodation and service spaces, the pipes conveying oil or combustible liquids shall be of a material approved by the Administration having regard to the fire risk.

2.3 Materials readily rendered ineffective by heat shall not be used for overboard scuppers, sanitary discharges, and other outlets which are close to the water-line and where the failure of the material in the event of fire would give rise to danger of flooding.

3 Electric radiators, if used, shall be fixed in position and so constructed as to reduce fire risks to a minimum. No such radiators shall be fitted with an element so exposed that clothing, curtains, or other similar materials can be scorched or set on fire by heat from the element.

4 Cellulose-nitrate based films shall not be used for cinematograph installations.

5 All waste-receptacles shall be constructed of non-combustible materials with no openings in the sides or bottom.

6 In spaces where penetration of oil products is possible, the surface of insulation shall be impervious to oil or oil vapours.

Regulation 19 International shore connexion * [* Reference is made to the recommendation contained in resolution A.470 (XII) adopted by the Organization entitled "International Shore Connexion (shore side)".] 1 Ships of 500 tons gross tonnage and upwards shall be provided with at least one international shore connexion, complying with provisions of paragraph 3.

2 Facilities shall be available enabling such a connexion to be used on either side of the ship.

3 Standard dimensions of flanges for the international shore connexion shall be in accordance with the following table: |------------------- | Description | Dimension | |--------|----------| | Outside diameter | 178 mm | |--------|----------| | Inside diameter | 64 mm | |--------|----------| | Bolt circle diameter | 132 mm | |--------|----------| | Slots in flange | 4 holes 19 mm in diameter spaced | | equidistantly on a bolt circle | | of the above diameter, slotted | | to the flange periphery | |--------|----------| | Flange thickness | 14.5 mm minimum | |--------|----------| | Bolts and nuts | 4, each of 16 mm diameter, | | 50 mm in length | |------------------- 4 The connexion shall be of steel or other suitable material and shall be designed for 1.0 2 N/mm services. The flange shall have a flat face on one side and on the other shall be permanently attached to a coupling that will fit the ship's hydrant and hose. The connexion 2 shall be kept aboard the ship together with a gasket of any material suitable for 1.0 N/mm services, together with four 16 mm bolts, 50 mm in length and eight washers.

Regulation 20 Fire control plans 1 In all ships general arrangement plans shall be permanently exhibited for the guidance of the ship's officers, showing clearly for each deck the control stations, the various fire sections enclosed by "A" class divisions, the sections enclosed by "B" class divisions together with particulars of the fire detection and fire alarm systems, the sprinkler installation, the fire-extinguishing appliances, means of access to different compartments, decks, etc. and the ventilating system including particulars of the fan control positions, the position of dampers and identification numbers of the ventilating fans serving each section. Alternatively, at the discretion of the Administration, the aforementioned details may be set out in a booklet, a copy of which shall be supplied to each officer, and one copy shall at all times be available on board in an accessible position. Plans and booklets shall be kept up to date, any alterations being recorded thereon as soon as practicable.

Description in such plans and booklets shall be in the national language.

If the language is neither English nor French, a translation into one of those languages shall be included. In addition, instructions concerning the maintenance and operation of all the equipment and installations on board for the fighting and containment of fire shall be kept under one cover, readily available in an accessible position.

2 In all ships a duplicate set of fire control plans or a booklet containing such plans shall be permanently stored in a prominently marked weathertight enclosure outside the deckhouse for the assistance of shoreside fire-fighting personnel.

Regulation 21 Ready availability of fire-extinguishing appliances In all ships, fire-extinguishing appliances shall be kept in good order and available for immediate use at all times during the voyage.

Regulation 22 Acceptance of substitutes 1 This Regulation applies to all ships.

2 Where in this Chapter any special type of appliance, apparatus, extinguishing medium or arrangement is specified in any ship, any other type of appliance etc., may be allowed, provided the Administration is satisfied that it is not less effective.

PART D FIRE SAFETY MEASURES FOR PASSENGER SHIPS
Regulation 23 Structure 1 The hull, superstructure, structural bulkheads, decks and deckhouses shall be constructed of steel or other equivalent material. For the purpose of applying the definition of steel or other equivalent material as given in Regulation 3.7 the "applicable fore exposure" shall be according to the integrity and insulation standards given in the tables of Regulation 26 and 27. For example where divisions such as decks or sides and ends of deckhouses are permitted to have "B-0" fire integrity, the "applicable fire exposure" shall be half an hour.

2 However, in cases where any part of the structure is of aluminium alloy, the following shall apply: .1 The insulation of aluminium alloy components of "A" or "B" class divisions, except structure which, in the opinion of the Administration, is non-load-bearing, shall be such that the temperature of the structural core does not rise more than 200 ¡æabove the ambient temperature at any time during the applicable fire exposure to the standard fire test.

.2 Special attention shall be given to the insulation of aluminium alloy components of columns, stanchions and other structural members required to support lifeboat and liferaft stowage, launching and embarkation areas, and "A" and "B" class divisions to ensure: .2.1 that for such members supporting lifeboat and liferaft areas and "A" class divisions, the temperature rise limitation specified in paragraph 2.1 shall apply at the end of one hour; and .2.2 that for such members required to support "B" class divisions, the temperature rise limitation specified in paragraph 2.1 shall apply at the end of half an hour.

3 Crowns and casings of machinery spaces of category A shall be of steel construction adequately insulated and openings therein, if any, shall be suitably arranged and protected to prevent the spread of fire.

Regulation 24 Main vertical zones and horizontal zones 1.1 For ships carrying more than 36 passengers, the hull, superstructure and deckhouses shall be subdivided into main vertical zones by "A" class divisions. Steps and recesses shall be kept to a minimum, but where they are necessary they shall also be "A" class divisions. These divisions shall have insulation values in accordance with tables in Regulation 26.

1.2 For ships carrying not more than 36 passengers, the hull, superstructure and deckhouses in way of accommodation and service spaces shall be subdivided into main vertical zones by "A" class division. These divisions shall have insulation values in accordance with tables in Regulation 27.

2 As far as practicable, the bulkheads forming the boundaries of the main vertical zones above the bulkhead deck shall be in line with watertight subdivision bulkheads situated immediately below the bulkhead deck.

3 Such bulkheads shall extend from deck to deck and to the shell or other boundaries.

4 Where a main vertical zone is subdivided by horizontal "A" class divisions into horizontal zones for the purpose of providing an appropriate barrier between sprinklered and non-sprinklered zones of the ship, the divisions shall extend between adjacent main vertical zone bulkheads and to the shell or exterior boundaries of the ship and shall be insulated in accordance with the fire insulation and integrity values given in table 26.3 or in table 27.2.

5.1 On ships designed for special purposes, such as automobile or railroad car ferries, where the provision of main vertical zone bulkheads would defeat the purpose for which the ship is intended, equivalent means for controlling and limiting a fire shall be substituted and specifically approved by the Administration.

5.2 However, in a ship with special category spaces, any such space shall comply with the applicable provisions of Regulation 37 and in so far as such compliance would be inconsistent with compliance with other requirements of this Part, the requirements of Regulation 37 shall prevail.

Regulation 25 Bulkheads within a main vertical zone 1.1 For ships carrying more than 36 passengers all bulkheads which are not required to be "A" class divisions shall be at least "B" class or "C" class divisions as prescribed in the tables in Regulation 26.

1.2 For ships carrying not more than 36 passengers all bulkheads within accommodation and service spaces which are not required to be "A" class divisions shall be at least "B" class or "C" class divisions as prescribed in the tables in Regulation 27.

1.3 All such divisions may be faced with combustible materials in accordance with the provisions of Regulation 34.

2 All corridor bulkheads where not required to be "A" class shall be "B" class divisions which shall extend from deck to deck except: .1 when continuous "B" class ceilings or linings are fitted on both sides of the bulkhead, the portion of the bulkhead behind the continuous ceiling or lining shall be of material which, in thickness and composition, is acceptable in the construction of "B" class divisions but which shall be required to meet "B" class integrity standards only in so far as is reasonable and practicable in the opinion of the Administration; .2 in the case of a ship protected by an automatic sprinkler system complying with the provisions of Regulation 12 the corridor bulkheads of "B" class materials may terminate at a ceiling in the corridor provided such a ceiling is of material which, in thickness and composition, is acceptable in the construction of "B" class divisions.

Notwithstanding the requirements of Regulations 26 and 27 such bulkheads and ceilings shall be required to meet "B" class integrity standards only in so far as is reasonable and practicable in the opinion of the Administration. All doors and frames in such bulkheads shall be of non-combustible materials and shall be so constructed and erected as to provide substantial fire resistance to the satisfaction of the Administration.

3 All bulkheads required to be "B" class divisions, except corridor bulkheads, shall extend from deck to deck and to the shell or other boundaries unless continuous "B" class ceilings or linings are fitted on both sides of the bulkhead, in which case the bulkhead may terminate at the continuous ceiling or lining.

Regulation 26 Fire integrity of bulkheads and decks in ships car-rying more than 36 passengers 1 In addition to complying with the specific provisions for fire integrity of bulkheads and decks mentioned elsewhere in this Part, the minimum fire integrity of all bulkheads and decks shall be as prescribed in tables 26.1 to 26.4. Where, due to any particular structural arrangements in the ship, difficulty is experienced in determining from the tables the minimum fire integrity value of any divisions, such values shall be determined to the satisfaction of the Administration.

2 The following requirements shall govern application of the tables: .1 Table 26.1 shall apply to bulkheads bounding main vertical zones or horizontal zones.

Table 26.2 shall apply to bulkheads not bounding either main vertical zones or horizontal zones.

Table 26.3 shall apply to decks forming steps in main vertical zones or bounding horizontal zones.

Table 26.4 shall apply to decks not forming steps in main vertical zones nor bounding horizontal zones.

.2 for the purpose of determining the appropriate fire integrity standards to be applied to boundaries between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (14) below. Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this Regulation, it shall be treated as a space within the relevant category having the most stringent boundary requirements. The title of each category is intended to be typical rather than restrictive. The number in parentheses preceding each category refers to the applicable column or row number in the tables.

(1) Control stations Spaces containing emergency sources of power and lighting.

Wheelhouse and chartroom.

Spaces containing the ship's radio equipment.

Fire-extinguishing rooms, fire control and recording stations.

Control room for propulsion machinery when located outside the propulsion machinery space.

Spaces containing centralized fire alarm equipment.

Spaces containing centralized emergency public address system stations and equipment.

(2) Stairways Interior stairways, lifts and escalators (other than those wholly contained within the machinery spaces) for passengers and crew and enclosures thereto.

In this connexion a stairway which is enclosed at only one level shall be regarded as part of the space from which it is not separated by a fire door.

(3) Corridors Passenger and crew corridors and lobbies.

(4) Lifeboat and liferaft handling and embarkation stations Open deck spaces and enclosed promenades forming lifeboat and liferaft embarkation and lowering stations.

(5) Open deck spaces Open deck spaces and enclosed promenades clear of lifeboat and liferaft embarkation and lowering stations.

Air space (the space outside superstructures and deckhouses).

(6) Accommodation spaces of minor fire risk Cabins containing furniture and furnishings of restricted fire risk.

Offices and dispensaries containing furniture and furnishings of restricted fire risk.

Public spaces containing furniture and furnishings of restricted fire risk and having a deck area of less than 50 square m .

(7) Accommodation spaces of moderate fire risk Spaces as in category (6) above but containing furniture and furnishings of other than restricted fire risk.

Public spaces containing furniture and furnishings of restricted fire risk and having a deck area of 50 square m or more.

Isolated lockers and small store-rooms in accommodation spaces.

Sale shops.

Motion picture projection and film stowage rooms.

Diet kitchens (containing no open flame).

Cleaning gear lockers (in which flammable liquids are not stowed).

Laboratories (in which flammable liquids are not stowed).

Pharmacies.

Small drying rooms (having a deck area of 4 square m or less).

Specie rooms.

(8) Accommodation spaces of greater fire risk Public spaces containing furniture and furnishings of other than restricted fire risk and having a deck area of 50 square m or more.

Barber shops and beauty parlours.

(9) Sanitary and similar spaces Communal sanitary facilities, showers, baths, water closets, etc.

Small laundry rooms.

Indoor swimming pool area.

Operating rooms.

Isolated pantries containing no cooking appliances in accommodation spaces.

Private sanitary facilities shall be considered a portion of the space in which they are located.

(10) Tanks, voids and auxiliary machinery spaces having little or no fire risk Water tanks forming part of the ship's structure.

Voids and cofferdams.

Auxiliary machinery spaces which do not contain machinery having a pressure lubrication system and where storage of combustibles is prohibited, such as: ventilation and air-conditioning rooms; windlass room; steering gear room; stabilizer equipment room; electrical propulsion motor room; rooms containing section switchboards and purely electrical equipment other than oil-filled electrical transformers (above 10 kVA); shaft alleys and pipe tunnels; spaces for pumps and refrigeration machinery (not handling or using flammable liquids).

Closed trunks serving the spaces listed above.

Other closed trunks such as pipe and cable trunks.

(11) Auxiliary machinery spaces, cargo spaces, special category spaces, cargo and other oil tanks and other similar spaces of moderate fire risk Cargo oil tanks.

Cargo holds, trunkways and hatchways.

Refrigerated chambers.

Oil fuel tanks (where installed in a separate space with no machinery).

Shaft alleys and pipe tunnels allowing storage of combustibles.

Auxiliary machinery spaces as in category (10) which contain machinery having a pressure lubrication system or where storage of combustibles is permitted.

Oil fuel filling stations.

Spaces containing oil-filled electrical transformers (above 10 kVA).

Spaces containing turbine and reciprocating steam engine driven auxiliary generators and small internal combustion engines of power output up to 110 kW driving emergency generators, sprinkler, drencher or fire pumps, bilge pumps, etc.

Special category spaces (tables 26.1 and 26.3 only apply).

Closed trunks serving the spaces listed above.

(12) machinery spaces and main galleys Main propulsion machinery rooms (other than electric propulsion motor rooms) and boiler rooms.

Auxiliary machinery spaces other than those in categories (10) and (11) which contain internal combustion machinery or other oil-burning, heating or pumping units.

Main galleys and annexes.

Trunks and casings to the spaces listed above.

(13) Store-rooms, workshops, pantries, etc.

Main pantries not annexed to galleys.

Main laundry.

Large drying rooms (having a deck area of more than 4 square m ).

Miscellaneous stores.

Mail and baggage rooms.

Garbage rooms.

Workshops (not part of machinery spaces, galleys, etc.) (14) Other spaces in which flammable liquids are stowed Lamp rooms.

Paint rooms.

Store-rooms containing flammable liquids (including dyes, medicines, etc.) Laboratories (in which flammable liquids are stowed).

.3 Where a single value is shown for the fire integrity of a boundary between two spaces, that value shall apply in all cases.

.4 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is not protected by an automatic sprinkler system complying with the provisions of Regulation 12 or between such zones neither of which is so protected, the higher of the two values given in the tables shall apply.

.5 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is protected by an automatic sprinkler system complying with the provisions of Regulation 12 or between such zones both of which are so protected, the lesser of the two values given in the tables shall apply.

Where a sprinklered zone and a non-sprinklered zone meet within accommodation and service spaces, the higher of the two values given in the tables shall apply to the division between the zones.

.6 Notwithstanding the provisions of Regulation 35 there are no special requirements for material or integrity of boundaries where only a dash appears in the tables.

.7 The Administration shall determine in respect of category (5) spaces whether the insulation values in table 26.1 or 26.2 shall apply to ends of deckhouses and superstructures, and whether the insulation values in table 26.3 or 26.4 shall apply to weather decks. In no case shall the requirements of category (5) of tables 26.1 to 26.4 necessitate enclosure of spaces which in the opinion of the Administration need not be enclosed.

3 Continuous "B" class ceilings or linings, in association with the relevant decks or bulkheads, may be accepted as contributing wholly or in part, to the required insulation and integrity of a division.

4 In approving structural fire protection details, the Administration shall have regard to the risk of heat transmission at intersections and terminal points of required thermal barriers.

TABLE 26.1 -BULKHEADS BOUNDING MAIN VERTICAL ZONES OR HORIZONTALZONES |------------------------------------ || | | | | | | | | Spaces || (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | (14) | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Control stations (1)|| A-60 | A-30 | A-30 | A-0 | A-0 | A-60 | A-60 | A-60 | A-0 | A-0 | A-60 | A-60 | A-60 | A-60 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Stairways (2)|| A-0 | A-0 | A-0 | A-0 | A-15 | A-30 | A-60 | A-0 | A-0 | A-30 | A-60 | A-15 | A-60 | || | | A-0 | A-0 | A-15 | | | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Corridors (3)|| | A-0 | A-0 | A-0 | A-0 | A-30 | A-30 | A-0 | A-0 | A-30 | A-60 | A-15 | A-60 | || | | | A-0 | A-0 | | | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Lifeboat and liferaft handling (4)|| | - | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | A-60 | | and embarkation stations || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Open deck spaces (5)|| | | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of mi- (6)|| | | A-15 | A-30 | A-30 | A-0 | A-0 | A-15 | A-30 | A-15 | A-30 | | nor fire risk || | | A-0 | A-0 | A-0 | | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (7)|| | | | A-30 | A-60 | A-0 | A-0 | A-30 | A-60 | A-30 | A-60 | | moderate fire risk || | | | A-0 | A-15 | | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (8)|| | | | A-60 | A-0 | A-0 | A-60 | A-60 | A-30 | A-60 | | greater fire risk || | | | A-15 | | A-15 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Sanitary and similar spaces (9)|| | | | | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Tanks, voids and auxiliary || | | | | | | | | machinery spaces having little (10)|| | | | | A-0 | A-0 | A-0 | A-0 | A-0 | | or no fire risk || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| | Auxiliary machinery spaces, (11)|| | | | | | A-0 | A-60 | A-0 | A-60 | | cargo spaces, special category || | | | | | | | | spaces, || | | | | | | | | cargo and other oil tanks and || | | | | | | | | other similar spaces of moder- || | | | | | | | | ate fire risk || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | b| | Machinery spaces and main (12)|| | | | | | A-60 | A-30 | A-60 | | galleys || | | | | | | A-15 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| | Store-rooms, workshops, (13)|| | | | | | | | | pantries etc. || | | | | | | A-0 | A-30 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Other spaces in which (14)|| | | | | | | A-60 | | flammable liquids are stowed || | | | | | | | || | | | | | | | |------------------------------------ -------- See notes under table 26.4 TABLE 26.2 -BULKHEADS NOT BOUNDING EITHER MAIN VERTICAL ZONES ORHORIZONTAL ZONES |------------------------------------ || | | | | | | | | Spaces || (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | (14) | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || a | | | | | | | | Control stations (1)|| B-0 | A-0 | A-0 | A-0 | A-0 | A-60 | A-60 | A-60 | A-0 | A-0 | A-60 | A-60 | A-60 | A-60 | || | | B-0 | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || a | | | | | | | | Stairways (2)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-15 | A-30 | A-0 | A-0 | A-15 | A-30 | A-15 | A-30 | || | | | A-0 | A-0 | | | A-30 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Corridors (3)|| | C | A-0 | A-0 | B-0 | B-15 | B-15 | B-0 | A-0 | A-15 | A-30 | A-0 | A-30 | || | | B-0 | B-0 | B-0 | | | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Lifeboat and liferaft handling (4)|| | - | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-15 | A-0 | A-15 | | and embarkation stations || | | | | | | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Open deck space (5)|| | | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | || | | B-0 | B-0 | B-0 | B-0 | | B-0 | B-0 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of mi- (6)|| | | B-0 | B-15 | B-15 | B-0 | A-0 | A-15 | A-30 | A-0 | A-30 | | nor fire risk || | | C | C | C | C | A-0 | | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (7)|| | | | B-15 | B-15 | B-0 | A-0 | A-15 | A-60 | A-15 | A-60 | | moderate fire risk || | | | C | C | C | A-0 | A-0 | A-15 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (8)|| | | | B-15 | B-0 | A-0 | A-30 | A-60 | A-15 | A-60 | | greater fire risk || | | | C | C | A-0 | A-0 | A-15 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Sanitary and similar spaces (9)|| | | | | C | A-0 | A-0 | A-0 | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Tanks, voids and auxiliary (10)|| | | | | a | | | | machinery spaces having little || | | | | A-0 | A-0 | A-0 | A-0 | A-0 | | or no fire risk || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Auxiliary machinery spaces, (11)|| | | | | | a | | b| | cargo spaces, cargo and other || | | | | | A-0 | A-0 | A-0 | A-30 | | oil tanks and other similar || | | | | | | A-15 | | spaces of moderate fire risk || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Machinery spaces and main (12)|| | | | | | a | | | galleys || | | | | | A-0 | A-0 | A-60 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Store-rooms, workshops, (13)|| | | | | | | a | | pantries, etc. || | | | | | | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | b| | Other spaces in which (14)|| | | | | | | A-30 | | flammable liquids are stowed || | | | | | | A-15 | || | | | | | | | |------------------------------------ -------- See notes under table 26.4 TABLE 26.3 -DECKS FORMING STEPS IN MAIN VERTICAL ZONES OR BOUNDINGHORIZONTAL ZONES |------------------------------------ || | | | | | | | | Space below ¡ý Space above¡ú || (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | (14) | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Control stations (1)|| A-60 | A-60 | A-30 | A-0 | A-0 | A-15 | A-30 | A-60 | A-0 | A-0 | A-30 | A-60 | A-15 | A-60 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Stairways (2)|| A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | A-15 | A-15 | A-0 | A-0 | A-0 | A-60 | A-0 | A-60 | || | | | A-0 | A-0 | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Corridors (3)|| A-30 | A-0 | A-0 | A-0 | A-0 | A-0 | A-15 | A-15 | A-0 | A-0 | A-0 | A-60 | A-0 | A-60 | || | | | A-0 | A-0 | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Lifeboat and liferaft handling (4)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | | and embarkation stations || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Open deck spaces (5)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of mi- (6)|| A-60 | A-30 | A-15 | A-0 | A-0 | A-0 | A-15 | A-30 | A-0 | A-0 | A-15 | A-15 | A-0 | A-15 | | nor fire risk || A-0 | A-0 | | A-0 | A-0 | | A-0 | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (7)|| A-60 | A-60 | A-30 | A-15 | A-0 | A-15 | A-30 | A-60 | A-0 | A-0 | A-30 | A-30 | A-0 | A-30 | | moderate fire risk || A-15 | A-0 | A-0 | A-0 | A-0 | A-15 | | A-0 | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (8)|| A-60 | A-60 | A-60 | A-60 | A-0 | A-30 | A-60 | A-60 | A-0 | A-0 | A-30 | A-60 | A-15 | A-60 | | greater fire risk || A-15 | A-15 | A-15 | A-0 | A-15 | A-15 | | A0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Sanitary and similar spaces (9)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Tanks, voids and auxiliary (10)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | | machinery spaces having little || | | | | | | | | or no fire risk || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| | Auxiliary machinery spaces, (11)|| | | | | | | b| | cargo spaces, special category || A-60 | A-60 | A-60 | A-60 | A-0 | A-30 | A-60 | A-60 | A-0 | A-0 | A-0 | A-30 | A-30 | A-30 | | spaces, cargo and other oil || | | A-0 | A-15 | A-15 | | | A-0 | | tanks and other similar spaces || | | | | | | | | of moderate fire risk || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Machinery spaces and main (12)|| A-60 | A-60 | A-60 | A-60 | A-0 | A-60 | A-60 | A-60 | A-0 | A-0 | A-60 | A-60 | A-60 | A-60 | | galleys || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Store-rooms, workshops, (13)|| A-60 | A-60 | A-30 | A-15 | A-0 | A-15 | A30 | A-60 | A-0 | A-0 | A-0 | A-30 | A-0 | A-30 | | pantries, etc. || A-15 | A-0 | | A-0 | A-0 | A-15 | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Other spaces in which (14)|| A-60 | A-60 | A-60 | A-60 | A-0 | A-60 | A-60 | A-60 | A-0 | A-0 | A-60 | A-60 | A-60 | A-60 | | flammable liquids are stowed || | | | | | | | || | | | | | | | |------------------------------------ -------- See notes under table 26.4 TABLE 26.4 -DECKS NOT FORMING STEPS IN MAIN VERTICAL ZONES NORBOUNDING HORIZONTAL ZONES |------------------------------------ || | | | | | | | | Space below ¡ý Space above¡ú || (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | (12) | (13) | (14) | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Control stations (1)|| A-30 | A-30 | A-15 | A-0 | A-0 | A-0 | A-15 | A-30 | A-0 | A-0 | A-0 | A-60 | A-0 | A-60 | || A-0 | A-0 | A-0 | B-0 | A-0 | A-0 | | | A-15 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Stairways (2)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-30 | A-0 | A-30 | || | | B-0 | | | | | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | a | | | | | | | Corridors (3)|| A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | A-15 | A-15 | A-0 | A-0 | A-0 | A-30 | A-0 | A-30 | || | a | | | | | | || A-0 | B-0 | B-0 | B-0 | B-0 | B-0 | B-0 | | | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Lifeboat and liferaft handling (4)|| A-0 | A-0 | A-0 | A-0 | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | | and embarkation stations || | | B-0 | B-0 | B-0 | B-0 | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Open deck spaces (5)|| A-0 | A-0 | A-0 | A-0 | - | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | || | B-0 | | B-0 | B-0 | B-0 | B-0 | | B-0 | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of mi- (6)|| A-60 | A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-15 | A-0 | A-15 | | nor fire risk || A-0 | | B-0 | B-0 | B-0 | B-0 | B-0 | | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (7)|| A-60 | A-30 | A-15 | A-15 | A-0 | A-0 | A-15 | A-30 | A-0 | A-0 | A-15 | A-30 | A-0 | A-30 | | moderate fire risk || A-0 | A-0 | A-0 | B-0 | B-0 | B-0 | B-0 | B-0 | A-0 | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Accommodation spaces of (8)|| A-60 | A-60 | A-60 | A-30 | A-0 | A-15 | A-30 | A-60 | A-0 | A-0 | A-30 | A-30 | A-0 | A-30 | | greater fire risk || A-15 | A-0 | A-0 | B-0 | B-0 | B-0 | B-0 | B-0 | A-0 | A-0 | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | | | Sanitary spaces and similar (9)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | | spaces || | B-0 | B-0 | B-0 | B-0 | B-0 | B-0 | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | a | | | | Tanks, voids and auxiliary (10)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | | machinery spaces having little || | | | | | | | | or no fire risk || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| | Auxiliary machinery spaces, (11)|| | | | | | a | | b| | cargo spaces, cargo and other || A-60 | A-60 | A-60 | A-30 | A-0 | A-0 | A-15 | A-30 | A-0 | A-0 | A-0 | A-0 | A-0 | A-30 | | oil tanks and other similar || A-15 | A-15 | A-0 | | A-0 | A-0 | | | A-15 | | spaces of moderate fire risk || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | a| | | Machinery spaces and main (12)|| A-60 | A-60 | A-60 | A-60 | A-0 | A-60 | A-60 | A-60 | A-0 | A-0 | A-30 | A-30 | A-0 | A-60 | | galleys || | | | | | | | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | | b| | Store-rooms, workshops, (13)|| A-60 | A-30 | A-15 | A-15 | A-0 | A-15 | A-30 | A-30 | A-0 | A-0 | A-0 | A-0 | A-0 | A-15 | | pantries, etc. || A-0 | A-0 | A-0 | B-0 | A-0 | A-0 | A-0 | B-0 | | | A-0 | || | | | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---|---|---|---| || | | | | | b| b| b| | Other spaces in which (14)|| A-60 | A-60 | A-60 | A-60 | A-0 | A-30 | A-60 | A-60 | A-0 | A-0 | A-30 | A-30 | A-0 | A-30 | | flammable liquids are stowed || A-30 | A-30 | | A-0 | A-15 | A-15 | | A-0 | A-0 | A-0 | || | | | | | | | |------------------------------------ Notes: To be applied to tables 26.1 to 26.4, as appropriate.

a Where adjacent spaces are in the same numerical category and superscript a appears, a bulkhead or deck between such spaces need not be fitted if deemed unnecessary by the Administration. For example, in category (12) a bulkhead need not be required between a galley and its annexed pantries provided the pantry bulkheads and decks maintain the integrity of the galley boundaries. A bulkhead is, however, required between a galley and a machinery space even though both spaces are in category (12).

b Where superscript b appears the lesser insulation value may be permitted only if at least one of the adjoining spaces is protected by an automatic sprinkler system complying with the provisions of Regulation 12.

Regulation 27 Fire integrity of bulkheads and decks in ships car-rying not more than 36 passengers 1 In addition to complying with the specific provisions for fire integrity of bulkheads and decks mentioned elsewhere in this Part, the minimum fire integrity of bulkheads and decks shall be as prescribed in table 27.1 and table 27.2.

2 The following requirements shall govern application of the tables: .1 Tables 27.1 and 27.2 shall apply respectively to the bulkheads and decks separating adjacent spaces.

.2 For determining the appropriate fire integrity standards to be applied to divisions between adjacent spaces, such spaces are classified according to their fire risk as shown in categories (1) to (11) below. The title of each category is intended to be typical rather than restrictive.

The number in parentheses preceding each category refers to the applicable column or row in the tables.

(1) Control stations Spaces containing emergency sources of power and lighting.

Wheelhouse and chartroom.

Spaces containing the ship's radio equipment.

Fire-extinguishing rooms, fire control stations and fire-recording stations.

Control room for propulsion machinery when located outside the machinery space.

Spaces containing centralized fire alarm equipment.

(2) Corridors Passenger and crew corridors and lobbies.

(3) Accommodation spaces Spaces as defined in Regulation 3.10 excluding corridors.

(4) Stairways Interior stairways, lifts and escalators (other than those wholly contained within the machinery spaces) and enclosures thereto.

In this connexion, a stairway which is enclosed only at one level shall be regarded as part of the space from which it is not separated by a fire door.

(5) Service spaces (low risk) Lockers and store-rooms having areas of less than 2 square m , drying rooms and laundries.

(6) Machinery spaces of category A Spaces as defined in Regulation 3.19.

(7) Other machinery spaces Spaces as defined in Regulation 3.20 excluding machinery spaces of category A.

(8) Cargo spaces All spaces used for cargo (including cargo oil tanks) and trunkways and hatchways to such spaces, other than special category spaces.

(9) Service spaces (high risk) Galleys, pantries containing cooking appliances, paint and lamp rooms, lockers and store-rooms having areas of 2 square m or more and workshops other than those forming part of the machinery spaces.

(10) Open decks Open deck spaces and enclosed promenades having no fire risk. Air spaces (the space outside superstructures and deckhouses).

(11) Special category spaces Spaces as defined in Regulation 3.18.

.3 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is not protected by an automatic sprinkler system complying with the provisions of Regulation 12 or between such zones neither of which is so protected, the higher of the two values given in the tables shall apply.

.4 In determining the applicable fire integrity standard of a boundary between two spaces within a main vertical zone or horizontal zone which is protected by an automatic sprinkler system complying with the provisions of Regulation 12 or between such zones both of which are so protected, the lesser of the two values given in the tables shall apply.

Where a sprinklered zone and a non-sprinklered zone meet within accommodation and service spaces, the higher of the two values given in the tables shall apply to the division between the zones.

3 Continuous "B" class ceilings or linings, in association with the relevant decks or bulkheads, may be accepted as contributing, wholly or in part, to the required insulation and integrity of a division.

4 External boundaries which are required in Regulation 23.1 to be of steel or other equivalent material may be pierced for the fitting of windows and sidescuttles provided that there is no requirement for such boundaries to have "A" class integrity elsewhere in this Chapter.

Similarly, in such boundaries which are not required to have "A" class integrity, doors may be of materials to the satisfaction of the Administration.

TABLE 27.1 -FIRE INTEGRITY OF BULKHEADS SEPARATING ADJACENT SPACES |------------------------------ || | | | | | | Spaces || (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| || c | | | | | | | Control stations (1)|| A-0 | A-0 | A-60 | A-0 | A-15 | A-60 | A-15 | A-60 | A-60 | * | A-60 | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| || e | e | e | e | | | | | Corridors (2)|| C | B-0 | B-0 | B-0 | A-60 | A-0 | A-0 | A-15 | * | A-15 | || | a | | | d | | || | A-0 | | | A-0 | | |----------||---|---|---|---|---|---|---|---|---|---|---| || | e | e | e | | | | | Accommodation Spaces (3)|| | C | B-0 | B-0 | A-60 | A-0 | A-0 | A-15 | * | A-30 | || | a | | | d | d | || | A-0 | | | A-0 | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| || | e | e | | | | | Stairways (4)|| | B-0 | B-0 | A-60 | A-0 | A-0 | A-15 | * | A-15 | || | a | a | | d | | || | A-0 | A-0 | | A-0 | * | |----------||---|---|---|---|---|---|---|---|---|---|---| || | | e | | | | | Service spaces (5)|| | | C | A-60 | A-0 | A-0 | A-0 | * | A-0 | | (low risk) || | | | | | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---| || | | | | | | Machinery spaces of category A (6)|| | | * | A-0 | A-0 | A-60 | * | A-60 | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| || | | | b | | | | Other machinery spaces (7)|| | | | A-0 | A-0 | A-0 | * | A-0 | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| || | | | | | | Cargo spaces (8)|| | | | * | A-0 | * | A-0 | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| || | | | | b | | | Service spaces (high risk) (9)|| | | | | A-0 | * | A-30 | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| || | | | | | | Open decks (10)|| | | | | - | A-0 | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| || | | | | | | Special category spaces (11)|| | | | | | A-0 | || | | | | | |------------------------------ Notes: To be applied to both tables 27.1 and 27.2, as appropriate.

a) For clarification as to which applies see Regulations 25 and 29.

b) Where spaces are of the same numerical category and superscript b appears, a bulkhead or deck of the ratings shown in the tables is only required when the adjacent spaces are for a different purpose, e.g. in category (9). A galley next to a galley does not require a bulkhead but a galley next to a paint room requires an "A-0" bulkhead.

c) Bulkheads separating the wheelhouse and chartroom from each other may be "B-0" rating.

d) See 2.3 and 2.4 of this Regulation.

e) For the application of Regulation 24.1.2, "B-0" and "C", where appearing in table 27.1, shall be read as "A-0".

f) Fire insulation need not be fitted if the machinery spaces of category (7), in the opinion of the Administration, has little or no fire risk.

* Where an asterisk appears in the tables, the division is required to be of steel or other equivalent material but is not required to be of "A" class standard.

For the application of Regulation 24.1.2 an asterisk, where appearing in table 27.2, except for categories (8) and (10), shall be read as "A-0".

TABLE 27.2 -FIRE INTEGRITY OF DECKS SEPARATING ADJACENT SPACES |------------------------------ || | | | | | | Spaces below ¡ý Space above¡ú || (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) | (10) | (11) | || | | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| | Control station (1)|| A-0 | A-0 | A-0 | A-0 | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-30 | |----------||---|---|---|---|---|---|---|---|---|---|---| | Corridors (2)|| A-0 | * | * | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| || A-60 | A-0 | * | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-30 | | Accommodation spaces (3)|| | | | | | d | || | | | | | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| | Stairways (4)|| A-0 | A-0 | A-0 | * | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| |----------||---|---|---|---|---|---|---|---|---|---|---| | Service spaces (low risk) (5)|| A-15 | A-0 | A-0 | A-0 | * | A-60 | A-0 | A-0 | A-0 | * | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| | Machinery spaces of category A (6)|| | | | f| | | || A-60 | A-60 | A-60 | A-60 | A-60 | * | A-60 | A-30 | A-60 | * | A-60 | |----------||---|---|---|---|---|---|---|---|---|---|---| | Other machinery spaces (7)|| A-15 | A-0 | A-0 | A-0 | A-0 | A-0 | * | A-0 | A-0 | * | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| | Cargo spaces (8)|| A-60 | A-0 | A-0 | A-0 | A-0 | A-0 | A-0 | * | A-0 | * | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| | Service spaces (9)|| A-60 | A-30 | A-30 | A-30 | A-0 | A-60 | A-0 | A-0 | A-0 | * | A-30 | | (high risk) || d | d | d | | | | || A-0 | A-0 | A-0 | | | | |----------||---|---|---|---|---|---|---|---|---|---|---| | Open decks (10)|| * | * | * | * | * | * | * | * | * | - | A-0 | |----------||---|---|---|---|---|---|---|---|---|---|---| || A-60 | A-15 | A-30 | A-15 | A-0 | A-30 | A-0 | A-0 | A-30 | A-0 | A-0 | | Special category spaces (11)|| | d | | | | | || | A-0 | | | | | |------------------------------ Regulation 28 Means of escape 1 Stairways and ladders shall be arranged to provide ready means of escape to the lifeboat and liferaft embarkation deck from all passenger and crew spaces and from spaces in which the crew is normally employed, other than machinery spaces. In particular, the following provisions shall be complied with: .1 Below the bulkhead deck two means of escape, at least one of which shall be independent of watertight doors, shall be provided from each watertight compartment or similarly restricted space or group of spaces. Exceptionally, the Administration may dispense with one of the means of escape, due regard being paid to the nature and location of spaces and to the number of persons who might normally be accommodated or employed there.

.2 Above the bulkhead deck there shall be at least two means of escape from each main vertical zone or similarly restricted space or group of spaces at least one of which shall give access to a stairway forming a vertical escape.

.3 If a radiotelegraph station has no direct access to the open deck, two means of escape from or access to such station shall be provided, one of which may be a porthole or window of sufficient size or another means to the satisfaction of the Administration.

.4 A corridor or part of a corridor from which there is only one route of escape shall not exceed: 13 m in length for ships carrying more than 36 passengers, and 7 m in length for ships carrying not more than 36 passengers.

.5 At least one of the means of escape required by paragraphs 1.1 and 1.2 shall consist of a readily accessible enclosed stairway, which shall provide continuous fire shelter from the level of its origin to the appropriate lifeboat and liferaft embarkation decks or the highest level served by the stairway, whichever level is the highest. However, where the Administration has granted dispensation under the provisions of paragraph 1.1 the sole means of escape shall provide safe escape to the satisfaction of the Administration. The width, number and continuity of the stairways shall be to the satisfaction of the Administration.

.6 Protection of access from the stairway enclosures to the lifeboat and liferaft embarkation areas shall be to the satisfaction of the Administration.

.7 Stairways serving only a space and a balcony in that space shall not be considered as forming one of the required means of escape.

2.1 In special category spaces the number and disposition of the means of escape both below and above the bulkhead deck shall be to the satisfaction of the Administration and in general the safety of access to the embarkation deck shall be at least equivalent to that provided for under paragraphs 1.1, 1.2, 1.5 and 1.6.

2.2 One of the escape routes from the machinery spaces where the crew is normally employed shall avoid direct access to any special category space.

3.1 Two means of escape shall be provided from each machinery space.

In particular, the following provisions shall be complied with: .1 Where the space is below the bulkhead deck the two means of escape shall consist of either: .1.1 two sets of steel ladders as widely separated as possible, leading to doors in the upper part of the space similarly separated and from which access is provided to the appropriate lifeboat and liferaft embarkation decks. One of these ladders shall provide continuous fire shelter from the lower part of the space to a safe position outside the space; or .1.2 one steel ladder leading to a door in the upper part of the space from which access is provided to the embarkation deck and additionally, in the lower part of the space and in a position well separated from the ladder referred to, a steel door capable of being operated from each side and which provides access to a safe escape route from the lower part of the space to the embarkation deck.

.2 Where the space is above the bulkhead deck, the two means of escape shall be as widely separated as possible and the doors leading from such means of escape shall be in a position from which access is provided to the appropriate lifeboat and liferaft embarkation decks. Where such means of escape require the use of ladders, these shall be of steel.

3.2 In a ship of less than 1,000 tons gross tonnage, the Administration may dispense with one of the means of escape, due regard being paid to the width and disposition of the upper part of the space; and in a ship of 1,000 tons gross tonnage and above, the Administration may dispense with one means of escape from any such space so long as either a door or a steel ladder provides a safe escape route to the embarkation deck, due regard being paid to the nature and location of the space and whether persons are normally employed in that space.

4 In no case shall lifts be considered as forming one of the required means of escape.

Regulation 29 Protection of stairways and lifts in accommodationand service spaces 1 All stairways shall be of steel frame construction except where the Administration sanctions the use of other equivalent material, and shall be within enclosures formed of "A" class divisions, with positive means of closure at all openings, except that: .1 a stairway connecting only two decks need not be enclosed, provided the integrity of the deck is maintained by proper bulkheads or doors in one 'tweendeck space.

When a stairway is closed in one 'tweendeck space, the stairway enclosure shall be protected in accordance with the tables for decks in Regulations 26 or 27; .2 stairways may be fitted in the open in a public space, provided they lie wholly within such public space.

2 Stairway enclosures shall have direct communication with the corridors and be of sufficient area to prevent congestion, having in view the number of persons likely to use them in an emergency. In so far as is practicable, stairway enclosures shall not give direct access to cabins, service lockers, or other enclosed spaces containing combustibles in which a fire is likely to originate.

3 Lift trunks shall be so fitted as to prevent the passage of smoke and flame from one 'tweendeck to another and shall be provided with means of closing so as to permit the control of draught and smoke.

Regulation 30 Openings in "A" class divisions 1 Except for hatches between cargo, special category, store, and baggage spaces, and between such spaces and the weather decks, all openings shall be provided with permanently attached means of closing which shall be at least as effective for resisting fires as the divisions in which they are fitted.

2 The construction of all doors and door frames in "A" class divisions, with the means of securing them when closed, shall provide resistance to fire as well as to the passage of smoke and flame, as far as practicable, equivalent to that of the bulkheads in which the doors are situated. Such doors and door frames shall be constructed of steel or other equivalent material. Watertight doors need not be insulated.

3 It shall be possible for each door to be opened and closed from each side of the bulkhead by one person only.

4 Fire doors in main vertical zone bulkheads and stairway enclosures, other than power-operated watertight doors and those which are normally locked, shall be of the self-closing type capable of closing against an inclination of 3.5 ¡ã opposing closure. The speed of door closure shall, if necessary, be controlled so as to prevent undue danger to persons. All such doors, except those that are normally closed, shall be capable of release from a control station, either simultaneously or in groups, and also individually from a position at the door. The release mechanism shall be so designed that the door will automatically close in the event of disruption of the control system; however, approved power-operated watertight doors will be considered acceptable for this purpose. Hold-back hooks not subject to control station release will not be permitted. When double swing doors are permitted, they shall have a latch arrangement which is automatically engaged by the operation of the door release system.

5 Where a space is protected be an automatic sprinkler system complying with the provisions of Regulation 12 or fitted with a continuous "B" class ceiling, openings in decks not forming steps in main vertical zones nor bounding horizontal zones shall be closed reasonably tight and such decks shall meet the "A" class integrity requirements in so far as is reasonable and practicable in the opinion of the Administration.

6 The requirements for "A" class integrity of the outer boundaries of a ship shall not apply to glass partitions, windows and sidescuttles.

Similarly, the requirements for "A" class integrity shall not apply to exterior doors in superstructures and deckhouses.

Regulation 31 Openings in "B" class divisions 1 Doors and door frames in "B" class divisions and means of securing them shall provide a method of closure which shall have resistance to fire as far as practicable equivalent to that of the divisions except that ventilation openings may be permitted in the lower portion of such doors.

Where such opening is in or under a door the total net area of any such opening or openings shall not exceed 0.05 square m . When such opening is cut in a door it shall be fitted with a grill made of non-combustible material. Doors shall be non-combustible.

2 The requirements for "B" class integrity of the outer boundaries of a ship shall not apply to glass partitions, windows and sidescuttles.

Similarly, the requirements for "B" class integrity shall not apply to exterior doors in superstructures and deckhouses. For ships carrying not more than 36 passengers, the Administration may permit the use of combustible materials in doors separating cabins from the individual interior sanitary spaces such as showers.

3 Where an automatic sprinkler system complying with the provisions of Regulation 12 is fitted: .1 openings in decks not forming steps in main vertical zones nor bounding horizontal zones shall be closed reasonably tight and such decks shall meet the "B" class integrity requirements in so far as is reasonable and practicable in the opinion of the Administration; and .2 openings in corridor bulkheads of "B" class materials shall be protected in accordance with the provisions of Regulation 25.

Regulation 32 Ventilation systems 1 Passenger ships carrying more than 36 passengers 1.1 The ventilation system of a passenger ship carrying more than 36 passengers shall, in addition to this part of this Regulation, also be in compliance with the requirements of Regulation 16.2 to 16.9.

1.2 In general, the ventilation fans shall be so disposed that the ducts reaching the various spaces remain within the main vertical zone.

1.3 Where ventilation systems penetrate decks, precautions shall be taken, in addition to those relating to the fire integrity of the deck required by Regulations 18.1.1 and 30.5, to reduce the likelihood of smoke and hot gases passing from one 'tweendeck space to another through the system. In addition to insulation requirements contained in this Regulation, vertical ducts shall, if necessary, be insulated as required by the appropriate tables in Regulation 26.

1.4 Except in cargo spaces, ventilation ducts shall be constructed of the following materials: .1 ducts not less than 0.075 square m in sectional area and all vertical ducts serving more than a single 'tweendeck space shall be constructed of steel or other equivalent material; .2 ducts less than 0.075 square m in sectional area other than the vertical ducts referred to in paragraph 1.4.1, shall be constructed of non-combustible materials. Where such ducts penetrate "A" or "B" class divisions due regard shall be given to ensuring the fire integrity of the division; .3 short lengths of duct, not in general exceeding 0.02 square m in sectional area nor 2 m in length, need not be non-combustible provided that all of the following conditions are met: .3.1 the duct is constructed of a material of restricted fire risk to the satisfaction of the Administration; .3.2 the duct is used only at the terminal end of the ventilation system; and .3.3 the duct is not located closer than 600 mm measured along its length to a penetration of an "A" or "B" class division, including continuous "B" class ceilings.

1.5 Where a stairway enclosure is ventilated, the duct or ducts shall be taken from the fan room independently of other ducts in the ventilation system and shall not serve any other space.

1.6 All power ventilation, except machinery space and cargo space ventilation and any alternative system which may be required under Regulation 16.6, shall be fitted with controls so grouped that all fans may be stopped from either of two separate positions which shall be situated as far apart as practicable. Controls provided for the power ventilation serving machinery spaces shall also be grouped so as to be operable from two positions, one of which shall be outside such spaces.

Fans serving power ventilation systems to cargo spaces shall be capable of being stopped from a safe position outside such spaces.

2 Passenger ships carrying not more than 36 passengers 2.1 The ventilation system of passenger ships carrying not more than 36 passengers shall be in compliance with Regulation 16.

Regulation 33 Windows and sidescuttles 1 All windows and sidescuttles in bulkheads within accommodation and service spaces and control stations other than those to which the provisions of Regulation 30.6 and of Regulation 31.2 apply, shall be so constructed as to preserve the integrity requirements of the type of bulkheads in which they are fitted.

2 Notwithstanding the requirements of the tables in Regulations 26 and 27: .1 all windows and sidescuttles in bulkheads separating accommodation and service spaces and control stations from weather shall be constructed with frames of steel or other suitable material. The glass shall be retained by a metal glazing bead or angle; .2 special attention shall be given to the fire integrity of windows facing open or enclosed lifeboat and liferaft embarkation areas and to the fire integrity of windows situated below such areas in such a position that their failure during a fire would impede the launching of, or embarkation into, lifeboats, or liferafts.

Regulation 34 Restricted use of combustible materials 1 Except in cargo spaces, mail rooms, baggage rooms, or refrigerated compartments of service spaces, all linings, grounds, ceilings and insulations shall be of non-combustible materials. Partial bulkheads or decks used to subdivide a space for utility or artistic treatment shall also be of non-combustible material.

2 Vapour barriers and adhesives used in conjunction with insulation, as well as insulation of pipe fittings, for cold service systems need not be non-combustible, but they shall be kept to the minimum quantity practicable and their exposed surfaces shall have qualities of resistance to the propagation of flame to the satisfaction of the Administration.

3 The following surfaces shall have low flame-spread characteristics: * [* Reference is made to Guidelines on the Evaluation of Fire Hazard Properties of Materials, adopted by the Organization by resolution A. 166 (ES.IV).] .1 exposed surfaces in corridors and stairway enclosures, and of bulkheads, wall and ceiling linings in all accommodation and service spaces and control stations; .2 concealed or inaccessible spaces in accommodation, service spaces and control stations.

4 The total volume of combustible facings, mouldings, decorations and veneers in any accommodation and service space shall not exceed a volume equivalent to 2.5 mm veneer on the combined area of the walls and ceilings. In the case of ships fitted with an automatic sprinkler system complying with the provisions of Regulation 12, the above volume may include some combustible material used for erection of "C" class divisions.

5 Veneers used on surfaces and linings covered by the requirements of paragraph 3 shall have a calorific value not exceeding 45 MJ/square m of the area for the thickness used.

6 Furniture in the corridors and stairway enclosures shall be kept to a minimum.

7 Paints, varnishes and other finishes used on exposed interior surfaces shall not be capable of producing excessive quantities of smoke and toxic products.

8 Primary deck coverings, if applied within accommodation and service space and control stations, shall be of approved material which will not readily ignite, or give rise to toxic or explosive hazards at elevated temperatures. * [* Reference is made to Improved/Provisional/Guidelines on Test Procedures for Primary Deck/Coverings, adopted by the Organization by resolution A. 214(VII).] Regulation 35 Details of construction 1 In accommodation and service spaces, control stations, corridors and stairways: .1 air spaces enclosed behind ceilings, panelling or linings shall be suitably divided by close-fitting draught stops not more than 14 m apart; .2 in the vertical direction, such enclosed air spaces, including those behind linings stairways, trunks, etc. shall be closed at each deck.

2 The construction of ceiling and bulkheads shall be such that it will be possible, without impairing the efficiency of the fire protection, for the fire patrols to detect any smoke originating in concealed and inaccessible places, except where in the opinion of the Administration there is no risk of fire originating in such places.

Regulation 36 Automatic sprinkler, fire detection and fire alarmsystems or automatic fire detection and fire alarm systems 1 In any ship to which this Part applies there shall be installed throughout each separate zone, whether vertical or horizontal, in all accommodation and service spaces and, where it is considered necessary by the Administration, in control stations, except spaces which afford no substantial fire risk (such as void spaces, sanitary spaces, etc.) either: .1 an automatic sprinkler, fire detection and fire alarm system of an approved type, complying with the provisions of Regulation 12 and so installed and arranged as to protect such spaces; or .2 a fixed fire detection and fire alarm system of an approved type, complying with the provisions of Regulation 13 and so installed and arranged as to detect the presence of fire in such spaces, except that the smoke detectors required by Regulation 13.2. 2 need not be provided.

Regulation 37 Protection of special category spaces 1 Provisions applicable to special category spaces whether above or below the bulkhead deck

| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |


Search China Hotels China Hotels:
Please Select a City:
Find Your Hotel With China Map
Check-in:
Show Calendar
Check-out:
Show Calendar
Currency Adults Child

Search China Flight Ticket China Flight:
One Way Round-Trip
Departure city:
Destination:
Departure date:
Return date:



China Cities:
China Introduction
Beijing Travel Info
Changchun Travel Info
Changsha Travel Info
Chengde Travel Info
Chengdu Travel Info
Chongqing Travel Info
Dali Travel Info
Dunhuang Travel Info
Guilin Travel Info
Haikou Travel Info
Hangzhou Travel Info
Harbin Travel Info
Nanning Travel Info
Ningbo Travel Info
Qingdao Travel Info
Shanghai Travel Info
Shenyang Travel Info
Shenzhen Travel Info
Suzhou Travel Info
Taian Travel Info
Tianjin Travel Info
Weihai Travel Info
Wuyishan Travel Info
Xiamen Travel Info
Xian Travel Info
Yangzhou Travel Info
Zhuhai Travel Info

China Hotels
Aksu
Alxa
Anqing
Anshan
Anshun
Anyang
Baishan
Baoding
Baoji
Baotou
Bazhong
Beidaihe
Beihai
Beijing
Bengbu
Binzhou
Bozhou
Cangzhou
ChangChun
Changde
Changsha
Changshu
Changzhi
Changzhou
Chaohu
Chaoyang
Chaozhou
Chengde
Chengdu
Chenzhou
Chifeng
Chongqing
Chuxiong
Chuzhou
Cixi
Dali
Dalian
Dandong
Daqing
Datong
Daxinanling
Daye
Dehong
Dengfeng
Deyang
Dezhou
Dongguan
Dongxing
Dongying
Dujiangyan
Dunhuang
Emeishan
Enshi
FangChengGang
Fenghua
Fenghuang
Foshan
Fuding
Fushun
Fuyang
Fuzhou
Ganzhou
Guang'an
Guangyuan
GuangZhou
Guilin
Guiyang
Haikou
Haining
Handan
Hangzhou
Harbin
Hefei
Hegang
Heihe
Hengshui
Hengyang
Hetian
Heyuan
Heze
Hohhot
HongKong
Huaian
Huaibei
Huaihua
Huainan
Huangshan
Huangshi
Huizhou
Hulunbeier
Huzhou
Ji'an
Jiamusi
Jiangmen
Jiangyin
Jiaozuo
Jiaxing
Jiayuguan
Jieyang
Jilin
Jinan
Jincheng
Jingdezhen
Jinggangshan
Jingmen
Jingzhou
Jinhua
Jining
Jinzhong
Jiuhuashan
Jiujiang
Jiuquan
Jiuzhaigou
Jixi
Jiyuan
Kaifeng
Kaiping
Karamay
Kashen
Korla
Kunming
Kunshan
Langfang
Lanzhou
Leshan
Lhasa
Lianyungang
Liaocheng
Liaoyang
Lijiang
Linfen
Linyi
Lishui
Liuzhou
Longyan
Loudi
Luoyang
Lushan
Maanshan
Macau
Maoming
Meishan
Meizhou
Mianyang
Mudanjiang
Nanchang
Nanchong
Nanjing
Nanning
Nanping
Nantong
Nanyang
Ningbo
Ningde
Ordos
Panjin
Panzhihua
Penglai
Pingxiang
Pingyao
Putian
Putuoshan
Qian'nan
Qiandaohu
Qiandongnan
Qidong
Qingdao
Qingyuan
Qinhuangdao
Qionghai
Qiqihaer
Qitaihe
Quanzhou
Qufu
Qujing
Quzhou
Rizhao
Ruian
Sanmenxia
Sanming
Sanya
Shanghai
Shangrao
Shangri-la
Shantou
Shanwei
Shaoguan
Shaoshan
Shaoxing
Shenyang
Shenzhen
Shijiazhuang
Shishi
Shiyan
Shouguang
Suining
Suizhou
Suqian
Suzhou(Jiangsu)
Taian
Taicang
Taiyuan
Taizhou(Jiangsu)
Taizhou(Zhejiang)
Tangshan
Tengchong
Tianjin
Tianshui
Tieling
Tonghua
Tongliao
Tongling
Tongren
Turpan
Urumqi
Wanning
Weifang
Weihai
Weinan
Wenshan
Wenzhou
Wuhai
Wuhan
Wuhu
Wuwei
Wuxi
Wuyishan
Wuzhishan
Wuzhou
Xiamen
Xian
Xian'ning
Xiangfan
Xiangtan
Xianyang
Xiaogan
Xichang
Xilinhot
Xingyi
Xining
Xinxiang
Xinyu
Xinzhou
Xishuangbanna
Xitang
Xuchang
Xuzhou
Ya'an
Yancheng
Yandangshan
Yangjiang
Yangquan
Yangshuo
Yangzhou
Yanji
Yantai
Yibin
Yichang
Yichun
Yichun(Jiangxi)
Yinchuan
Yingkou
Yining
Yiwu
Yixing
Yiyang
Yongzhou
Yueqing
Yueyang
Yulin(Guangxi)
Yulin(Shaanxi)
Yuncheng
Yunfu
Zaozhuang
Zhangjiagang
Zhangjiajie
Zhangjiakou
Zhangzhou
Zhanjiang
Zhaoqing
Zhengzhou
Zhenjiang
Zhongshan
Zhongwei
Zhoukou
Zhoushan
Zhouzhuang
Zhuhai
Zhuji
Zhuzhou
Zibo
Zigong
Zunyi
| Home | Hotels | Hotels Video | China Flights | Flights Schedule | Pickup Service | Travel Packages | Affiliate | Add your hotels | Interprete Italiano-Cinese | Contact | Site Map | Link | FAQ | About Us
Copyright © 2001-2024 China Hotels Reservation - All Rights Reserved
Europe Office: ChinaHotelsReservation- Via Gerolamo Forni 64 - 20161 Milano - Fax 0291390522
China Office: China Travel(Hualv) Business co.,Ltd. - Tel 0086-577-88555070 Fax 0086-577-88522570
Xishan Donglu Xicen Gongyu 7 Zhuang 802 - 325005 Wenzhou China